beautypg.com

Flexprogrammer, Ex-confi guring, Confi guring with flexprogrammer – Baumer Flex Top 2211 User Manual

Page 2: Led function

background image

Page 2

Design and specifi cations subject to change without notice

Installation Manual 5850-032

www.baumer.com

The FlexTop 2211 can be confi gured, us ing the 4...20 mA cable.
The max i mum dis tance de pends on the cable type, re sist ance and
ca pac i ty. We rec om mend to use screened cables.

To be able to confi gure the FlexTop 2211 with the FlexProgrammer the
dedicated software, Flex-program, must be loaded on the PC.

The Flex-program has help menus for all func tions.

During the confi guration the new data are, by means of the FlexPro-
grammer, trans ferred from the PC to the FlexTop 2211, where they are
stored in the in ter nal mem o ry.

Ex-Confi guring

None of the two types of FlexProgrammer confi guring unit must be
connected to the FlexView within the hazardous area.

Confi guring procedure:
a) Disconnect mains from the 4...20 mA loop circuit.
b) Disconnect the FlexTop 2211 from the circuitry within

the hazardous area.

c) Bring the FlexTop 2211 to the safe area.
d) Connect the FlexProgrammer and perform the
confi

guring

session.

e) Re-install the FlexTop 2211 in the hazardous area.
f) Connect the power supply to the circuit.

Note:
Disconnect loop supply before
connecting the FlexProgrammer
to FlexTop 2211.

2 1

Confi guring with FlexProgrammer

2

1

FlexProgrammer

1

2

Note: Ambient temperature range 0...50°C

FlexProgrammer

FlexProgrammer 9701

1

2

Red clip

Black clip

The indication for a correct con fi g u ra tion se quence is:

1) The LED on the FlexTop 2211 lights up constantly.

Error indications during confi guration:
1) The LED on the FlexTop 2211 is not lighting.

3) An error message comes up on the PC.

Note: During the fi rst power-up after a confi guration the power-on time
increases to approx. 10 sec.

The LED of the FlexTop indicate the actual status of the measured
value. The LED will be turned on continually as long as the measured
value result in an output current between 4 and 20mA. If the output
current is higher than 20mA or lower than 4mA the LED will twinkle
with 1Hz. The same twinkling behavior will occur if a sensor break
error is detected.

LED Function