6. Error warnings
Error warnings are visualized by a flashing upper display line, indicating alternately both error signal and current
value (usually target).
MAX limit of SPA hurt by manual positioning operation (by softkey)
Troubleshooting: Set SPA to the admissible positioning range.
MIN limit of SPA hurt by manual positioning operation (by softkey)
Troubleshooting: Set SPA to the admissible positioning range.
SPA is giving a motor start signal but N 142 hollow shaft does not move.
Troubleshooting: Check motor, cable and mechanical connections from motor to shaft to SPA.
Motor failure at SPA.
(Failure is indicated for approx 5 seconds if motor start is released by interface or
pushbutton)
Troubleshooting: Take corrective actions.
SPA did not reach the target window.
Troubleshooting: Extend the tolerance window. Set switchover to precision speed at an earlier
point.
Direction error. Shaft positioning is in the wrong direction.
Troubleshooting: Verify SPA parameterization ( for example motor direction of rotation, or motor
cable connection)
Target transmitted respectively DIM parameter is above the MAX limit.
Note: Consider any loops.
Troubleshooting: Transmit new valid position value.
Target transmitted respectively DIM parameter is below the MIN limit.
Note: Consider any loops.
Troubleshooting: Transmit new valid position value.