Extended identifier command „ax“ (41h,58h), N 142 – Baumer N 142 User Manual
Page 26
N 142
www.baumer.com
26
Indicate identifier in the display, command „A“ (41h)
This command less parameters as a broadcast command (address/Identifier=99) will make every networked N
142 indicate the device-specific identifier in the bottom line of the display. The upper line is blind.
This command is a designated broadcast command.
SOH Adr Cmd EOT CRC
Transmission
01h 83h 41h 04h 80h
Response
Not confirmed
The SPA remains in this mode until being switched off and on again or until transmission of another command.
Extended identifier command „AX“ (41h,58h)
This extended command is utilized for addressing individual multicon devices in the bus network in a similar
way as described above. By broadcast command the identifier to be assigned is transmitted to all networked
devices as follows:
SOH
Adr
Cmd
Sub Identifier = 01
EOT
CRC
Transmission
01h
83h
41h
58h
30h
31h
04h
40h
Response
Not confirmed
Similar to standard command all devices now show the identifier just transmitted and that is to be assigned in
the upper line. Entering the identifier is proceeded the same way. However contrary to the above no
confirmatory command „B“ will be replied. It is up to master to check whether the identifier has been accepted,
for example by command “R” (read current value). The R-command is transmitted under the corresponding
identifier to the position display. If the addressed SPA replies the assignment was successful and the master
can proceed with the next identifier. With other commands the display of the respective device switches to
standard operation.