Setting the baud rate, Terminating resistor, Bus cover connection – Baumer G1-G2-G0-GE-GB-GXxxx User Manual
Page 15
Manual_DeviceNet_BIDE_EN.docx
15/18
Baumer IVO GmbH & Co. KG
22.11.12
Villingen-Schwenningen, Germany
10.2.2 Setting the baud rate
The baud rate setting is binary, using switches 2 and 3 of the 3-pin DIP switch in the bus cover.
The default value is 125 KBit/s.
Baud rate
Setting of the 3 DIP switches
Switch 1
Switch 2
Switch 3
125 kBit/s
X
OFF
OFF
250 kBit/s
X
OFF
ON
500 kBit/s
X
ON
OFF
125 kBit/s *
X
ON
ON
X = don`t care
* As this switch setting is not defined, it is set internally to the default value 125 kbit/s.
10.2.3 Terminating resistor
If the connected encoder is the last device in the bus line, the bus must be terminated with a resistor.
The resistor is in the bus cover and is connected using a DIP switch.
The terminating resistor must be switched to "ON" at the last user with a DIP switch (default setting OFF).
ON = Final user
OFF = User X
Switch 1:
ON = Final user
OFF = User X
Switch 2:
Without function
10.2.4 Bus cover connection
Release the cap nut of the cable gland.
Push the cap nut and seal insert with contact sleeve onto the cable sheath.
Strip the cable sheath and cores, remove the braided screen and shield film completely as far as the end
of the cable sheath.
The braided screen, shield film and Drain connector of the cable must not touch the housing.
Push the sealing insert with contact sleeve along as far as the braided shield. Insert the sealing insert
with contact sleeve and cable flush into the cable gland and tighten the cap nut.
Insert the cores into the terminal strip and screw tight, observing the admissible core cross-section
Use isolated core end sleeves. Use preferably isolated twin core end sleeves for supply voltage.
For standard encoder
For G0AMH, G0MMH, GBAMH and GBMMH