2 inputs, 1 analog sensor connection (sign) – Dynalco SWTD-1000 Speed Switch/Transmitter User Manual

Page 5

background image

Operating Instructions SWTD-1000

DYNALCO

3

//

Max. frequency against input voltage

0.01

0.1

1

10

100

0.001

0.01

0.1

1

10

100

1000

10000

100000

Frequency [Hz]

Input v

o

lt

a

g

e

[V

e

ff]

Trigger: 500mVpp

Trigger: 20mVeff

O.K.

NOT O.K.

3.2 Inputs

3.2.1 Analog Sensor connection (Sign)

Frequency range (-3dB)

0.01 Hz / 35 kHz

Input impedance

30 K

Input voltage

• Max.

80V

rms


Signal voltage [V

pp

] 0.5 1 2.5 5 10 20

Min. pulse width [µs]

2000

667

333

200

166

125

Minimum positive pulse
width - digital signals Input
voltage

Integrated pull-up

820 Ohm to +V of the sensor supply (with Jumper J1)

Trigger level

adaptive Trigger level.
Configurable with Jumper J2:
• 250mV … 6.5V (>500mVpp) [Factory configuration]

• 28mV … 6.5V (>20mV

rms

)

Screen

A terminal is provided for the sensor cable screen. This terminal is connected to
the sensor supply 0V. (0VS)

Sensor monitoring

1 of 3 settings may be configured via software:
• No Sensor Monitoring

• Monitoring of powered sensors

[Also for 2 wire sensors supplied via the Pull-up resistor (Jumper J1) ].
Æ The sensor is considered to be defective if the sensor current
consumption falls outside of I

min

and I

max

.

I

min.

= 0.5…25 mA

I

max.

= 0.5…25 mA

• Monitoring of non powered sensors

[For 2 wire sensors such as electromagnetic sensors.]
Æ The sensor is considered to be defective if the circuit is disconnected.