4 parameter list and ranges – Dynalco SWTD-1000 Speed Switch/Transmitter User Manual
Page 15
Operating Instructions SWTD-1000
DYNALCO
13
//
8.4 Parameter List and Ranges
If you already have a configuration file you can open and view it using the SWTD-1000 Windows
Software menu
File
Æ Open
You can also connect the SWTD-1000 to a PC (see section 8.2) and read back the parameters,
SWTD-1000
Æ Read parameters
Once loaded into the software the parameter set may be printed via File
Æ Print
Normal Windows file handling rules apply.
Parameter list and ranges. Factory settings are shown in bold.
Configuration < System >
Machine factor
1.0000E-07 ... 1.0000 ... 9.9999E+07
Minimum Measuring time
2 / 5 / 10 / 20 / 50/ 100 / 200 / 500 ms / 1/ 2 / 5 Seconds
Min displayed measured value
1.0000E-12 ... 1 ... 1.0000E+12
Alarm definition
Only System error System error OR Sensor Monitoring
Configuration < Sensor >
Sensor Type
Active / Passive
Sensor input
Analog (Sign) / Digital (IQ)
Sensor current minimum
0.5 ... 1.5 ... 25.0mA
Sensor current maximum
0.5 ... 25.0mA
Configuration < Analog output >
Measuring range start value
0.0000 ... 90% of the end value
Measuring range end value
1Hz … 2000.0 … 500000
Output range
0 ... 20mA / 4 ... 20mA
Time constant (Damping)
0.0 ... 9.9s
Configuration < Limits >
Status Limit
1
On / Off
Status Limit
2
On / Off
Mode Limit
1
Normal / Inverse
Mode Limit
2
Normal / Inverse
Lower Set point
Limit 1
0.1 … 200.00 … 500000
Upper Set point
Limit 1
0.1 … 300.00 … 500000
Lower Set point
Limit 2
0.1 … 400.00 … 500000
Upper Set point
Limit 2
0.1 … 500.00 … 500000
Configuration < Relay control >
Switching of control A/B
Selection of actuator
None (always control A) / Binary Input B1
Delay time
0 ... 2.000 s
Relay Assignment
Control
A
Alarm / Sensor monitor / Limit 1 / Limit 2 / Window / On / Off
Acknowledge A
Without acknowledge (no hold function) /
Relay held when control active /
Relay held when control inactive
Acknowldge
B
Alarm / Sensor monitor / Limit 1 / Limit 2 / Window / On / Off
Acknowldge
B
Without acknowledge (no hold function) /
Relay held when control active /
Relay held when control inactive