Operating Instructions SWTD-1000

DYNALCO

15

//

8.5.3 Analog Output (Configuration

Æ Analog Output)

21

20

12

4

0

speed
[RPM]

0...20mA mode

4...20mA mode

initial value

final value

(minimal measured

value)

[mA]


Measuring range – start value

Analog output start value 0 or 4mA

Measuring range – end value

Analog output end value 20mA
In the case of a negative transfer function the end value must be set smaller than the start value.

Output range

0…20mA or 4…20mA

Output time constant

The analog output signal may be smoothed by applying a software time constant. This damping is
deactivated when the time constant is 0.0 seconds.

8.5.4 Limit (Configuration

Æ Limit)

The SWTD-1000 series offers 2 independent limits

Æ Limit 1 and 2.

Status

Limits are selected here. If the limit is deactivated, the other values such as set points and mode have
no further effect.

Mode

In Normal Mode the limit is active as soon as the High set point is exceeded. In Inverse Mode the limit is
active from the start (zero speed) and deactivates when the set point is reached (Fail Safe operation)

Upper and Lower Set point

rpm

limit

activated

deactivated

lower

switching point

upper
switching point

As the speed increases, the limit switches when the High set point is reached and remains in that
condition until the speed reduces past the Low set point.