beautypg.com

Dynalco UM-600 Universal Monitor User Manual

Page 4

background image

3

Additional Features

• 5 - Digit Hourmeter Function (non-resettable)

• Engine RPM Display

• Fully programmable from front keypad

• ¼ DIN package (3 ½” width X 3 ½” height) for panel mount


Specifications

Input Types

J or K type thermocouple (ungrounded)
4 - 20 mA
0 – 1 VDC
0 - 5 VDC
0 – 10 VDC

Digital Input

Closure to ground indicates run condition (or use pulsed input)

Pulsed Input

Magnetic pickup input for RPM display & to indicate run condition

Alarm Outputs

2 Digital Outputs rated @ 0.15 A / 48 VDC

Input Power

10 – 36 VDC

Display

Backlit Graphic Display

Data Logging

Internal Flash Memory to retain data logged values w/ date & time stamp

Communications

Modbus

Connections

Two-Part Terminal Blocks

Operating Temperature Range

- 40 to + 70 Deg C

Certification

CSA Class I, Division 2, Groups A, B, C, D


User Interface

The UM-600 is configured via the keypad on the front panel which includes a graphical backlit
LCD display capable of displaying alpha numeric values and custom engineering units of
measure. The keypad implements a menu system, which is navigated using the up, down,
left, right, enter and escape buttons. The backlight will turn off after ten minutes of inactivity
and will turn on when any of the keys are pressed.

Installation:

The UM-600 monitor is a standard ¼ DIN package, designed to be panel mounted. The
cutout dimensions are shown below.