3
Additional Features
• 5 - Digit Hourmeter Function (non-resettable)
• Engine RPM Display
• Fully programmable from front keypad
• ¼ DIN package (3 ½” width X 3 ½” height) for panel mount
Specifications
Input Types
J or K type thermocouple (ungrounded)
4 - 20 mA
0 – 1 VDC
0 - 5 VDC
0 – 10 VDC
Digital Input
Closure to ground indicates run condition (or use pulsed input)
Pulsed Input
Magnetic pickup input for RPM display & to indicate run condition
Alarm Outputs
2 Digital Outputs rated @ 0.15 A / 48 VDC
Input Power
10 – 36 VDC
Display
Backlit Graphic Display
Data Logging
Internal Flash Memory to retain data logged values w/ date & time stamp
Communications
Modbus
Connections
Two-Part Terminal Blocks
Operating Temperature Range
- 40 to + 70 Deg C
Certification
CSA Class I, Division 2, Groups A, B, C, D
User Interface
The UM-600 is configured via the keypad on the front panel which includes a graphical backlit
LCD display capable of displaying alpha numeric values and custom engineering units of
measure. The keypad implements a menu system, which is navigated using the up, down,
left, right, enter and escape buttons. The backlight will turn off after ten minutes of inactivity
and will turn on when any of the keys are pressed.
Installation:
The UM-600 monitor is a standard ¼ DIN package, designed to be panel mounted. The
cutout dimensions are shown below.