beautypg.com

Dynalco UM-600 Universal Monitor User Manual

Page 22

background image

21

302048-

302049

2047-

2048

Channel 6 High Low Limit

-9999.0

99999.0

32 bit Float(IEEE 754)

302050-

302051

2049-

2050

Channel 1 and 2 Differential Low
Alarm Limit

-9999.0

99999.0

32 bit Float(IEEE 754)

302052-

302053

2051-

2052

Channel 3 and 4 Differential Low
Alarm Limit

-9999.0

99999.0

32 bit Float(IEEE 754)

302054-

302055

2053-

2054

Channel 5 and 6 Differential Low
Alarm Limit

-9999.0

99999.0

32 bit Float(IEEE 754)

302056-

302057

2055-

2056

RPM

0

99999.0

32 bit unsigned integer

302058-

302059

2057-

2058

Hourmeter

0

99999.0

32 bit unsigned integer









Holding Register Table (table 2)

Modicon

Address

Modbus

Offset

Description

Min

Value

Max

Value

Data type

401001-

401002

1000-1001

Log start date (upper 16 bits
and lower 16 bits
respectively)

Custom (See table 3)


Date Format Table (table 3)

Second(MSB)

Minute

Hour

Day

Month

Year(LSB)

Bits

6

6

5

5

4

6

Value
range

0-59

0-59

0-23

1-31

1-12

0-63(relative to year
2000)

Log Buffer Entry (table 4)

Datetime

Event ID

Value

Length

32 bit unsigned
integer

16 bit unsigned
integer

32 bit Float(IEEE 754)

Value
range

See table 3

1-10

-9999.0 – 99999.0