Table 2. Algorithm List
Algorithm Battery
Type Charger
Type Algorithm
Type Description
1
Flooded
Controlled Ferro
Normal DVDT
Phase 1: Constant current at the start rate until 2.38 v/c.
Lead-Acid
HF
Phase 2: Constant Voltage at 2.38 v/c until dvdt or the current falls to 5A/100Ah
Phase 3: Constant Current at 5A/100Ah until dvdt.
Phase 4: not used.
*Additional Settings: start rate = SA parameter.
2
Flooded
Ferro-Resonant
Normal DVDT
Phase 1: Full output until 2.38 v/c.
Lead-Acid
Phase 2: Full output until dvdt.
Phase 3: not used.
Phase 4: not used.
3
Flooded
Ferro-Resonant
Hysteresis
Phase 1: Full output until 2.38 v/c.
Lead-Acid
Phase 2: Full output until dvdt.
Phase 3: Charger off until voltage drops to the hysteresis point, then reverts to phase 1.
Phase 4: not used.
*Additional Settings: hysteresis point = SV parameter.
4
Champion Sealed
Controlled Ferro
Normal DVDT
Phase 1: Constant current at 16.5A/100Ah until 2.37 v/c.
HF
Phase 2: Constant voltage at 2.37v/c until the current falls to 2.5A/100Ah or 5 hours.
Phase 3: Constant current at 2.5A/100Ah until dvdt or 2.55v/c.
Phase 4: Constant voltage at 2.55v/c until dvdt or 30 minutes.
5
Champion Sealed
Ferro-Resonant
Normal DVDT
Phase 1: Full output until 2.37 v/c.
Phase 2: Full output until dvdt or 2.52v/c.
Phase 3: not used.
Phase 4: not used.
6
Sonnenschein gel
Controlled Ferro
Special
Phase 1: Constant current at 16.5A/100Ah until 2.35v/c.
HF
Phase 2: Constant voltage at 2.35v/c until the current falls to 1.3A/100Ah.
Phase 3: Constant current at 1.3A/100Ah for 1 to 4 hours depending on time so far.
Phase 4: not used.
Note: Equalize occurs 10 hours after the charge at 0.6A/100Ah.
7
Deka gel
Controlled Ferro
Float
Phase 1: Constant Current at 15.5A/100Ah until 2.33v/c.
HF
Phase 2: Constant voltage at 2.33v/c until the current falls to 0.3A/100Ah or 10 hours.
Phase 3: not used.
Phase 4: not used.
8
Saft Ni-Cad
Controlled Ferro
Special
Phase 1: Constant current at 20A/100Ah until 1.59v/c or 6 1/2 hours.
HF
Phase 2: Constant current at 5A/100Ah until 15% more Ah are put in.
Phase 3: not used.
Phase 4: not used.
9 DO
NOT
USE
* Refer to table 1 for information on how to program Additional Settings.
continued