Table 2. Algorithm List

Algorithm Battery

Type Charger

Type Algorithm

Type Description

1

Flooded

Controlled Ferro

Normal DVDT

Phase 1: Constant current at the start rate until 2.38 v/c.

Lead-Acid

HF

Phase 2: Constant Voltage at 2.38 v/c until dvdt or the current falls to 5A/100Ah

Phase 3: Constant Current at 5A/100Ah until dvdt.

Phase 4: not used.

*Additional Settings: start rate = SA parameter.

2

Flooded

Ferro-Resonant

Normal DVDT

Phase 1: Full output until 2.38 v/c.

Lead-Acid

Phase 2: Full output until dvdt.

Phase 3: not used.

Phase 4: not used.

3

Flooded

Ferro-Resonant

Hysteresis

Phase 1: Full output until 2.38 v/c.

Lead-Acid

Phase 2: Full output until dvdt.

Phase 3: Charger off until voltage drops to the hysteresis point, then reverts to phase 1.

Phase 4: not used.

*Additional Settings: hysteresis point = SV parameter.

4

Champion Sealed

Controlled Ferro

Normal DVDT

Phase 1: Constant current at 16.5A/100Ah until 2.37 v/c.

HF

Phase 2: Constant voltage at 2.37v/c until the current falls to 2.5A/100Ah or 5 hours.

Phase 3: Constant current at 2.5A/100Ah until dvdt or 2.55v/c.

Phase 4: Constant voltage at 2.55v/c until dvdt or 30 minutes.

5

Champion Sealed

Ferro-Resonant

Normal DVDT

Phase 1: Full output until 2.37 v/c.

Phase 2: Full output until dvdt or 2.52v/c.

Phase 3: not used.

Phase 4: not used.

6

Sonnenschein gel

Controlled Ferro

Special

Phase 1: Constant current at 16.5A/100Ah until 2.35v/c.

HF

Phase 2: Constant voltage at 2.35v/c until the current falls to 1.3A/100Ah.

Phase 3: Constant current at 1.3A/100Ah for 1 to 4 hours depending on time so far.

Phase 4: not used.

Note: Equalize occurs 10 hours after the charge at 0.6A/100Ah.

7

Deka gel

Controlled Ferro

Float

Phase 1: Constant Current at 15.5A/100Ah until 2.33v/c.

HF

Phase 2: Constant voltage at 2.33v/c until the current falls to 0.3A/100Ah or 10 hours.

Phase 3: not used.

Phase 4: not used.

8

Saft Ni-Cad

Controlled Ferro

Special

Phase 1: Constant current at 20A/100Ah until 1.59v/c or 6 1/2 hours.

HF

Phase 2: Constant current at 5A/100Ah until 15% more Ah are put in.

Phase 3: not used.

Phase 4: not used.

9 DO

NOT

USE

* Refer to table 1 for information on how to program Additional Settings.

continued