Table 1. Programmable Parameter List

First Key Second

Key Third

Key

Parameter(s)

Description

Allowable Settings

Default

Notes

Locked

SET SET none

none

n/a

n/a

n/a

SET

1 (AMPS)

None

SA

Set Amps

0.0-100.0 (A/100Ah)

0.0

3

SET

2 (VOLTS)

None

SV

Set Volts

0.0-999.9 (V)

0.0

3

SET

3 (AH)

None

CR

Cable Resistance

0-25 (mΩ)

2

SET START None

TS

DS

PS
EP

Time of Day Start

Delayed Start

Energy Management Peak Start

Energy Management Peak End

00:00-23:59; 99:99 (disable)

00:00-24:00 (hh:mm)

00:00-23:59; 99:99 (disable)
00:00-23:59; 99:99 (disable)

99:99
00:00
99:99
99:99

SET

4 (TOC)

None

ST

Set Charge Time

00:00-99:99 (hh:mm) (99:99 runs forever)

00:00

3

SET 5 SET

none

n/a

n/a

n/a

SET

5

1 (AMPS)

WA

Watering Enable

0 (disable); 1 (every cycle); 2 (after equalize)

0

WC

Watering Cycles

0-60 (15s ON/ 45s OFF)

0

SET

5

2 (VOLTS)

CV

Charge Cutoff Voltage

1.40-3.55 (v/c)

2.80

2

SET

5

3 (AH)

EC

Equalize by Number of Charges

0-100

7

2

ED

Equalize by Day

0(disable); 1-7(Sun-Sat)

0

2

DE

Equalize Delay Time

00:00-24:00 (hh:mm)

00:00

2

SET 5

START

AL

Charge

Algorithm

1-17

n/a

1

SET

5

4 (TOC)

VR

Battery Voltage Rating

12-999 (V)

24

SET

5

5 (VER.)

SR

Charger Shunt Rating

0(current sensor); 50-600 (A)

200

SET

5

6 (I.D.)

EM

Equalize Mode

0 (None); 1(Normal)

1

2

EI

Equalize Current

0.1-10.0 (A/100Ah)

5.0

2

SET 5

CLOCK

MO

Month

1-12 (Jan-Dec)

n/a

DY

Day (of the month)

1-31

n/a

YR

Year

0-99 (years since 2000)

n/a

SET 5

7

(TEMP)

CT
TU

Cool Down Time

Count Up/Down

00:00-24:00 (hh:mm)

0(count down); 1(count up)

0:00

0

SET

5

8 (% RET.)

AR

Auto Refresh Time

00:00-72:00 (hh:mm) (0:00 disables)

0:00

SET

5

9 (80%)

TP

DVDT Trip Point

1.20-2.55 (v/c)

2.38

2

SET

5

ENTER

N2

F2 Indication Disable

0 (enable); 1 (disable)

1

2

N3

F3 Indication Disable

0 (enable); 1 (disable)

0

2

N4

F4 Indication Disable

0 (enable); 1 (disable)

0

2

N6

F6 Indication Disable

0 (enable); 1 (disable)

0

2

SET

5

=

ET

Equalize Time

00:00-24:00 (hh:mm)

3:00

2

SET

5

0 (TEST)

AO

Alert On Enable

0 (disable); 1 (enable)

1

AI

Alert Interval

10-60 (s)

60

SET

5

STOP

BC

Battery Module Comm. Enable

0 (disable); 1 (enable); 2 (enable and upload alg.)

0

SET

6 (I.D.)

None

ID

Charger I.D. (for Tobi or I'm Cool)

1-1000; 9999

9999

SET CLOCK

none

TD

Time of Day (Clock)

00:00-23:59 (hh:mm)

n/a

SET

7 (TEMP)

none

OT

OK to Charge Temp

0-185 (˚F) (0 disables sensor)

0

2

LT

NT

Low Charge Temp

No Charge Temp

0-185 (˚F)
0-185 (˚F)

115
125

2
2

SET

8 (% RET.)

none

CF

Charge Back Factor

0-150 (% of AH rating) (0 disables)

120

SET

9 (80%)

none

MP

Max Power Rating

0.1-25.0 (kW)

3.3

2

SET ENTER none

custom alg.

1,2,3

SET

=

none

CU

DVDT Periods

0-15 (5 minutes each)

5

SET

0 (TEST)

none

BS

Battery AH Rating

100-2200 (Ah)

0

SET

STOP

none

AS

Auto Start Mode

0 (manual start); 1 (auto start); 2 (auto start on ac)

1

Notes:

1. The Algorithm is set for the particular charger and battery type. If you are unsure of which algorithm to use, consult factory before setting.

2. These parameters are part of the algorithm. Any changes made to these are overwritten whenever the algorithm parameter is set.

3. These parameters are only used for certain algorithms. Consult the factory before changing any unfamiliar parameters.