Table 1. programmable parameter list – Exide Technologies GB4127 User Manual
Page 18
Table 1. Programmable Parameter List
First Key Second
Key Third
Key
Parameter(s)
Description
Allowable Settings
Default
Notes
Locked
SET SET none
none
n/a
n/a
n/a
SET
1 (AMPS)
None
SA
Set Amps
0.0-100.0 (A/100Ah)
0.0
3
●
SET
2 (VOLTS)
None
SV
Set Volts
0.0-999.9 (V)
0.0
3
●
SET
3 (AH)
None
CR
Cable Resistance
0-25 (mΩ)
2
SET START None
TS
DS
PS
EP
Time of Day Start
Delayed Start
Energy Management Peak Start
Energy Management Peak End
00:00-23:59; 99:99 (disable)
00:00-24:00 (hh:mm)
00:00-23:59; 99:99 (disable)
00:00-23:59; 99:99 (disable)
99:99
00:00
99:99
99:99
SET
4 (TOC)
None
ST
Set Charge Time
00:00-99:99 (hh:mm) (99:99 runs forever)
00:00
3
●
SET 5 SET
none
n/a
n/a
n/a
SET
5
1 (AMPS)
WA
Watering Enable
0 (disable); 1 (every cycle); 2 (after equalize)
0
WC
Watering Cycles
0-60 (15s ON/ 45s OFF)
0
SET
5
2 (VOLTS)
CV
Charge Cutoff Voltage
1.40-3.55 (v/c)
2.80
2
●
SET
5
3 (AH)
EC
Equalize by Number of Charges
0-100
7
2
ED
Equalize by Day
0(disable); 1-7(Sun-Sat)
0
2
DE
Equalize Delay Time
00:00-24:00 (hh:mm)
00:00
2
SET 5
START
AL
Charge
Algorithm
1-17
n/a
1
●
SET
5
4 (TOC)
VR
Battery Voltage Rating
12-999 (V)
24
●
SET
5
5 (VER.)
SR
Charger Shunt Rating
0(current sensor); 50-600 (A)
200
●
SET
5
6 (I.D.)
EM
Equalize Mode
0 (None); 1(Normal)
1
2
●
EI
Equalize Current
0.1-10.0 (A/100Ah)
5.0
2
●
SET 5
CLOCK
MO
Month
1-12 (Jan-Dec)
n/a
DY
Day (of the month)
1-31
n/a
YR
Year
0-99 (years since 2000)
n/a
SET 5
7
(TEMP)
CT
TU
Cool Down Time
Count Up/Down
00:00-24:00 (hh:mm)
0(count down); 1(count up)
0:00
0
SET
5
8 (% RET.)
AR
Auto Refresh Time
00:00-72:00 (hh:mm) (0:00 disables)
0:00
SET
5
9 (80%)
TP
DVDT Trip Point
1.20-2.55 (v/c)
2.38
2
●
SET
5
ENTER
N2
F2 Indication Disable
0 (enable); 1 (disable)
1
2
N3
F3 Indication Disable
0 (enable); 1 (disable)
0
2
●
N4
F4 Indication Disable
0 (enable); 1 (disable)
0
2
●
N6
F6 Indication Disable
0 (enable); 1 (disable)
0
2
●
SET
5
=
ET
Equalize Time
00:00-24:00 (hh:mm)
3:00
2
●
SET
5
0 (TEST)
AO
Alert On Enable
0 (disable); 1 (enable)
1
AI
Alert Interval
10-60 (s)
60
SET
5
STOP
BC
Battery Module Comm. Enable
0 (disable); 1 (enable); 2 (enable and upload alg.)
0
SET
6 (I.D.)
None
ID
Charger I.D. (for Tobi or I'm Cool)
1-1000; 9999
9999
SET CLOCK
none
TD
Time of Day (Clock)
00:00-23:59 (hh:mm)
n/a
SET
7 (TEMP)
none
OT
OK to Charge Temp
0-185 (˚F) (0 disables sensor)
0
2
LT
NT
Low Charge Temp
No Charge Temp
0-185 (˚F)
0-185 (˚F)
115
125
2
2
SET
8 (% RET.)
none
CF
Charge Back Factor
0-150 (% of AH rating) (0 disables)
120
●
SET
9 (80%)
none
MP
Max Power Rating
0.1-25.0 (kW)
3.3
2
●
SET ENTER none
custom alg.
1,2,3
●
SET
=
none
CU
DVDT Periods
0-15 (5 minutes each)
5
●
SET
0 (TEST)
none
BS
Battery AH Rating
100-2200 (Ah)
0
SET
STOP
none
AS
Auto Start Mode
0 (manual start); 1 (auto start); 2 (auto start on ac)
1
Notes:
1. The Algorithm is set for the particular charger and battery type. If you are unsure of which algorithm to use, consult factory before setting.
2. These parameters are part of the algorithm. Any changes made to these are overwritten whenever the algorithm parameter is set.
3. These parameters are only used for certain algorithms. Consult the factory before changing any unfamiliar parameters.