12 programming – Exide Technologies GB4127 User Manual
Page 14
13
2.1.12 Programming
To enter programming mode, press and hold the EDIT button and while holding it, press the INFO button. The display
shows a message describing the current parameter followed by the parameter‘s value. While in programming mode, the
buttons have the following functions:
STOP: Exit programming mode and save all parameters
=: Shift position of parameter being edited
EDIT: Change value of current position of parameter being edited
INFO: Change parameter to edit
Some of the parameters may be locked out in the programming mode. If a parameter is locked, the parameter is
displayed along with the current value and a lock is displayed on the left side of the display. The parameter can not be
changed. Refer to jumper settings section for information on locking out parameters. The following parameters are
available for editing:
PARAMETER MESSAGE
RANGE
NOTES
LOCK
BS
BATTERY AH SIZE
100-2200AH
VR BATTERY
VOLTAGE 12-999V
●
SR
SHUNT RATING
0-600A
A setting of 0 enables current sensor operation
●
AS AUTO
START
MODE 0-2
0: Manual Start
1: Auto-Start
2: Auto Start (restart on AC power)
CR CABLE
RESISTANCE 0-25mΩ
SA
START A/100AH
5.0-50.0 A/100AH
●
TP
80% TRIP POINT
2.35-2.45 V/C
●
FA
FINISH A/100AH
0.1-10.0 A/100AH
●
FV
FINISH VOLTAGE
2.50-3.00 V/C
●
CV
CUTOFF VOLTAGE
2.50-3.00 V/C
Exceeding this voltage terminates the charge immediately.
●
ST 80%
TIMEOUT 0:00-24:00
Exceeding this time results in an F1 if F1 is enabled and ends
normally if F1 is disabled. (see N1 parameter)
●
FT CHARGE
TIMEOUT 0:00-24:00
Exceeding this time results in an F7 if F7 is enabled and ends
normally if F7 is disabled. (see N7 parameter)
●
MP
MAX POWER RATING
0.1-25.0 kW
*DO NOT EXCEED RATING OF CHARGER
●
CF CHARGE
FACTOR 0-150%
Maximum return based on battery AH size. Setting this to 0 disables
the charge factor.
●
DS
DELAY START TIME
0:00-24:00
CT
COOL DOWN TIME
0:00-24:00
CU DVDT
PERIODS 0-15
Each period is 5 minutes. Setting this to 0 causes the charge to
terminate when the trip point is reached. (opportunity charge)
●
EM EQUALIZE
MODE
0-1
0: Equalize disabled
1: Normal equalize
●
EI EQUALIZE
A/100AH
0.1-10.0
A/100AH
●
ET EQUALIZE
TIME 0:00-24:00
●
EC
EQUALIZE CYCLES
0-30
Setting this to 0 disables automatic equalize.
N1
F1 FAULT DISABLE
0-1
0: Enabled, 1: Disabled
●
N3
F3 FAULT DISABLE
0-1
0: Enabled, 1: Disabled
●
N4
F4 FAULT DISABLE
0-1
0: Enabled, 1: Disabled
●
N6
F6 FAULT DISABLE
0-1
0: Enabled, 1: Disabled
●
N7
F7 FAULT DISABLE
0-1
0: Enabled, 1: Disabled
●
AR
REFRESH TIME
00:00-72:00
Setting this to 0:00 disables automatic refresh.