F X 5 T E C H N I C A L D ATA F O R 5 0 H Z
E L E C T R I C H E AT E R S
C US
Model
Note
Air Flow
V
oltage
Nominal
W
attage
Phase
Max. Motor Nameplate
Current
Heater W
attage
Total
Current
Minimum Circuit Ampacity
Supply W
ire
Maximum Fuse Size
Temperature
Rise
Core Kit
Part Number
Contactor
Part
Number
(CFM) (V) (kW)
(W)
(A)
(A)
(AWG)
(A)
°F
°C
FX5-220150-025
400
220
2.5
1
2.7
2270
11.4
14.3
14
15
19.8
11.0 12122
3618
FX5-220150-042
400
220
4.2
1
2.7
3950
19.1
23.9
10
25
33.2
18.4 12123
3618
FX5-220150-063
700
220
6.3
1
2.7
6050
28.6
35.8
8
40
28.5
15.8 12124
3618
FX5-220150-084
700
220
8.4
1
2.7
8140
38.2
47.8
6
50
37.9
21.1 12125
3619
FX5-220150-126
* 1450 220 12.6 1
1.4
12100 57.3
71.6
2
75
27.5
15.3 12126
3619
FX5-230150-028
400
230
2.8
1
2.7
2480
12.2
15.3
12
20
22.1
12.3 12122
3618
FX5-230150-046
400
230
4.6
1
2.7
4310
20.0
25.0
10
25
36.4
20.2 12123
3618
FX5-230150-069
700
230
6.9
1
2.7
6610
30.0
37.5
8
40
31.2
17.3 12124
3618
FX5-230150-138
* 1450 230 13.8 1
1.4
13200 59.9
74.9
2
80
30.1
16.7 12126
3619
FX5-380350-025
400
380
2.5
3
0.7
2270
3.8
4.8
16
5
19.8
11.0 12122
3618
FX5-380350-042
400
380
4.2
3
0.7
3950
6.4
8.0
16
10
33.2
18.4 12123
3618
FX5-380350-063
700
380
6.3
3
0.7
6050
9.6
12.0
14
15
28.5
15.8 12124
3618
FX5-380350-084
700
380
8.4
3
0.7
8140
12.8
16.0
12
20
37.9
21.1 12125
3618
FX5-380350-125
1450 380 12.5 3
0.7
12100 19.0
23.8
10
25
27.3
15.1 12126
3618
FX5-380350-209
3000 380 20.9 3
1.0
20300 31.8
39.8
8
40
22.0
12.2 12128
3618
FX5-400350-028
400
400
2.8
3
0.7
2480
4.0
5.0
16
5
22.1
12.3 12122
3618
FX5-400350-046
400
400
4.6
3
0.7
4310
6.6
8.3
16
10
36.4
20.2 12123
3618
FX5-400350-069
700
400
6.9
3
0.7
6610
10.0
12.5
14
15
31.2
17.3 12124
3618
FX5-400350-093
700
400
9.3
3
0.7
8900
13.4
16.8
12
20
42.0
23.3 12125
3618
FX5-400350-139
1450 400 13.9 3
0.7
13200 20.1
25.1
10
30
30.3
16.8 12126
3618
FX5-400350-185
1450 400 18.5 3
0.7
17800 26.7
33.4
8
35
40.3
22.4 12127
3618
FX5-400350-231
3000 400 23.1 3
1.0
22200 33.3
41.6
8
45
24.3
13.5 12128
3619
FX5-415350-037
400
415
3.7
3
0.7
3510
5.1
6.4
16
10
29.3
16.3 12130
3618
FX5-415350-075
700
415
7.5
3
0.7
7240
10.4
13.0
14
15
33.9
18.8 12132
3618
FX5-415350-149
1450 415 14.9 3
0.7
14500 20.7
25.9
10
30
32.5
18.1 12134
3618
FX5-415350-224
3000 415 22.4 3
1.0
21800 31.2
39.0
8
40
23.6
13.1 12136
3618
FX5-440350-042
400
440
4.2
3
0.7
3950
5.5
6.9
16
10
33.2
18.4 12130
3618
FX5-440350-084
700
440
8.4
3
0.7
8140
11.0
13.8
14
15
37.9
21.1 12132
3618
FX5-440350-168
1450 440 16.8 3
0.7
16300 27.5
34.4
8
35
36.6
20.4 12134
3618
FX5-440350-210
3000 440 21.0 3
1.0
20300 27.5
34.4
8
35
22.1
12.3 12135
3618
NOTES:
* Exceeds the 48 Amp Circuit Limit of NEC 424-22. DS5 not available for these units.
1. Minimum conductor size for 86˚F (30˚C) ambient. Derate conductor for ambient temperature. Use minimum 194˚F (90˚C) insulation.
2. Heater is functioning normally if at rated voltage the amp draw is within 10% of the value in this table.
3. Operation at lower voltages will result in reduced heat output and amp draw
4. Add "T" to model number when adding a built-in thermostat
5. Add "D" to model number when adding a built-in disconnect switch
6. Add "P" to model number when adding a built-in pilot light
7. Add "S" to model number when adding a 3-way switch
8. Add "H" to model number for units with high "off" (deenergized) ambient temperatures
9. Add "U" to model number for units with continuous fan option.
10. Add "A" to model number for units with stainless steel cabinet.