Item Field

Range

Access

Description

30 to 230 seconds

Default = 105

Ad

MIX MOTOR
The time that the actuating motor requires to operate
from fully closed to fully open.

Note:

This item is only available when the Mix Mode

setting is set to floating action (FLt).

OFF, 80 to 180°F

(OFF, 26.5 to 82.0°C)

Default = 140°F

(60.0°C)

InS

Ad

BOILER MINIMUM

SECTION D

The minimum allowed boiler target temperature and
boiler return protection temperature. Check the boiler
manufacturer’s manual for recommend supply water
temperatures.

Au, 2 to 42°F

(Au, 1 to 23.5°C)

Default = Au

Ad

BOILER DIFFERENTIAL

SECTION D

The temperature differential that the control is to use
when it is operating the boiler.

Note:

This item is only available when the Boiler

Sensor Sup / Ret DIP switch is set to Sup and the
tN4 DIP switch is set to Boiler.

Au, 5 to 30 min

Default = Au

Ad

CYCLES PER HOUR
The cycle length that all tN4 device heating zones
will synchronize to.

NONE, Mbr1, Mbr2,

Mbr3, Mbr4

Default = NONE

InS

Ad

SCHEDULE
Selects which network setback schedule the control
will follow.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 70°F (21.0°C)

InS

Ad

WWSD OCCUPIED

SECTION B

The system’s warm weather shut down temperature
during the Wake and Occupied periods.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 60°F (15.5°C)

Ad

WWSD UNOCCUPIED

SECTION B

The system’s warm weather shut down temperature
during the Sleep and Unoccupied period.

Note:

This item is only available when the Schedule

is not set to OFF.

Adjust Menu (2 of 2)

ADJUS

T MENU

After the last item, the control returns to the first item in the menu.