Item Field

Range

Access

Description

-60 to 45°F

(-51.0 to 7.0°C)

Default = 10°F

(-12.0°C)

InS

Ad

OUTDOOR DESIGN

SECTION B

The design outdoor air temperature used in the heat
loss calculations for the heating system. Typically set
to the temperature of the coldest day of the year.

VAr, FLt

Default = VAr

InS

Ad

MIX MODE
Select the type of mixing device to be used for mixing.
Options are variable speed injection pump (VAr) or
floating action (FLt).

1 HRF1

2 HRF2

3 Fancoil

4 Fin-tube Convector

5 Radiator

6 Baseboard
Default = 1

InS

Ad

MIX TERMINAL

SECTION B

The type of heating terminal units that are being
used in the mix temperature zones.

40 to 100°F

(4.5 to 38.0°C)

Default = 70°F (21.0°C)

Ad

MIX INDOOR

SECTION B

The design indoor air temperature used in the heat
loss calculation for mix zones. Typically set to 70°F
(21.0°C).

70 to 220°F

(21.0 to 104.5°C)

Default = 120°F

(49.0°C)

InS

Ad

MIX DESIGN

SECTION B

The supply water temperature required for the mix
temperature zones on the typical coldest day of the
year.

OFF, 40 to 150°F

(OFF, 4.5 to 65.5°C)

Default = OFF

Ad

MIX MINIMUM

SECTION C

The minimum allowed mix target temperature.

80 to 220°F, OFF

(26.5 to 104.5°C, OFF)

Default = 140°F

(60.0°C)

Ad

MIX MAXIMUM

SECTION C

The maximum allowed mix target temperature.

Adjust Menu (1 of 2)

The Adjust Menu items are the programmable settings
used to operate the mechanical equipment.

Continued on next page.

ADJUS

T MENU