View Menu (1 of 1)
Item Field
Range
Access
Description
-76 to 149°F
(-60.0 to 65.0°C)
InS
Ad
OUTDOOR
SECTION B
Current outdoor air temperature as measured by the
outdoor sensor.
-22 to 266°F
(-30.0 to 130.0°C)
InS
Ad
MIX SUPPLY
SECTION B
Current mix supply water temperature as measured
by the mix supply sensor.
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
Ad
MIX TARGET
SECTION C
The Mix target is the temperature the control is
currently trying to maintain at the mix supply sensor.
“– – –“ is displayed when no heat is required for mix
zones.
-22 to 266°F
(-30.0 to 130.0°C)
InS
Ad
BOILER SUPPLY
SECTION C
Current boiler supply water temperature as measured
by the boiler sensor.
Note:
This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
-22 to 266°F
(-30.0 to 130.0°C)
InS
Ad
BOILER RETURN
Current boiler return water temperature as measured
by the boiler sensor.
Note:
This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Ret.
0 to 9999 hr
InS
Ad
BOILER RUN TIME
The total running time of the boiler since this item
was last cleared. To clear this item, press the Up
and Down buttons simultaneously while viewing
this item.
Note:
This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
The View menu items display the current operating
temperatures and status information of the system.
VIEW MENU
Display Menus
After the last item, the control returns to the first item in the menu.