8. Critical Settings (Continued)

Display

Range

Access

Description

°F or °C
Default =
°F

Installer
User

TEMPERATURE UNITS

Press the

or the

button to

change from °F to °C and vice
versa.

Set To:

0, 1, 2, 3
Default = 1

Installer

FAN MODE

Select how the fan should operate
together with heating and cooling.
0 = Manual operation only
1 = Operate fan with cooling only
2 = Operate fan with heating and
cooling
3 = Operate fan with heating only

Set To:

Hyd
(Hydronic)
or Oth
(Other)
Default =
Hydronic

Installer

HEATING TERMINAL TYPE
Select if the heating for this zone
is hydronic or non-hydronic (other).
Available when:

• A reset control is present on

the tekmarNet

®

system.

Set To:

H1

H1

ADJUST

ADJUST

SUPPLY

On or Off
Default =
On

Installer

HEAT SUPPLY PUMP
During heating, select whether or
not the system supply pump should
turn on or be off to allow a zone
group pump per manifold.
Available when:

• A reset control is present on

the tekmarNet

®

system AND

Heating terminal type is set to
Hydronic.

Set To: