Press menu button until the Adjust Menu is displayed. Press item button
to locate the desired setting.

Item Field

Range

Access

Description

Set to

ADJUST

-60 to 45°F

(-51.0 to 7.0°C)

Default = 10°F

(-12.0°C)

Installer

OUTDOOR DESIGN
Typically set to the temperature of the coldest day of
the year. The outdoor air temperature used in the boiler
and mixing heating curves that determine the boiler
target and the mix target temperatures.

ADJUST

70 to 180°F

(21.0 to 82.0°C)
Default = 120°F

(49.0°C)

Installer

MIX DESIGN
The supply water temperature required for the mix
zones to heat the building on the typical coldest day
of the year. Recommendations:
High mass radiant floor = 120°F (50°C)
Low mass radiant floor = 140°F (60°C)
Fancoil or air handling unit = 190°F (90°C)
Copper fin-tube convector = 180°F (80°C)
Radiators = 160°F (70°C)
Low profile baseboard = 150°F (65°C)

ADJUST

4-20 mA,

0-10 V (dc)

FLOT,

VAR

Default = VAR

Installer

MIX TYPE

Select the type of mixing device.
VAR = Variable speed injection pump
FLOT = Floating action motor for mixing valves
0-10 = 0 -10 V (dc) analog signal for mixing valves
4-20 = 4-20 mA analog signal for mixing valves
Note: 0-10 and 4-20 are only available when Boiler
Type = 1 Stage or 2 Stage.

EMS2,

EMS1,

4-20

0-10,

2STG,

1STG

Default = 1STG

Installer

BOILER TYPE
The type of boiler connected to the control.
1STG = single one-stage on-off boiler
2STG = single two-stage on-off boiler
0-10 = 0-10 V (dc) modulating boiler
4-20 = 4-20 mA modulating boiler
EMS1 = tekmar boiler staging controls
EMS2 = Viessmann modulating boilers with
OpenTherm
Note: Only 1STG and 2STG are available when the
Mix Type is set to 0-10 V (dc) or 4-20 mA.

11.

Critical Settings