Note: Depending on the settings the installer makes in the control, certain items may not appear.

Item

Range

Lt

d

Us

er

364 View Menu

Current outdoor air temperature as measured by the outdoor
sensor. This is the default display for the control.

Target room air temperature. “ –––” denotes no heat is required.

Measured room air temperature at the indoor sensor.

Current operating status of the snow melting system.

Current mixed supply water temperature as measured by the
mixing sensor.

Current boiler supply water temperature as measured by the boiler
sensor.

Current boiler return water temperature as measured by the boiler
sensor.

Target DHW tank temperature. This item can only be viewed if a
tekmar sensor is used to measure the DHW tank temperature.

Current DHW tank temperature as measured by the DHW tank
sensor.

-67 to 149°F
(-55 to 65°C)

–––, 35 to 100°F
(2 to 38°C)

-58 to 167°F
(-50 to 75°C)

STRT, STOP, IDLE, EXT,
0:00 to 17:00 hr,

–––,

INF, WWSD, CWCO

-31 to 266°F
(-35 to 130°C)

-31 to 266°F
(-35 to 130°C)

-31 to 266°F
(-35 to 130°C)

-31 to 266°F
(-35 to 130°C)

–––, OFF, 70 to 190°F
(21 to 88°C)

Item

Range

Lt

d

Us

er

364 Adjust Menu

This item is the desired slab surface temperature while in the
melting mode.

This item is the time that the slab is operated for once it has
reached the MELTING temperature. This item can only be viewed
if a Remote Start / Stop Module 039 has not been connected.

The desired room air temperature for the mixing zones.
Note: There is only a ±3°F (±1°C) adjustment in the LTD access level.

The minimum temperature at the slab sensor as long as the control
is not in WWSD. This item can only be adjusted if a tekmar sensor
is connected.

The desired room air temperature for the boiler zones.
Note: There is only a ±3°F (±1°C) adjustment in the LTD access level.

The desired DHW storage tank temperature. This item can only
be adjusted if a tekmar sensor is used to measure the DHW tank
temperature.

The system’s warm weather shut down temperature.

32 to 95°F
(0 to 35°C)

OFF, 0:30 to 17:00 hrs,
INF (Infinite)

35 to 100°F
(2 to 38°C)

OFF, 35 to 120°F
(2 to 49°C)

35 to 100°F
(2 to 38°C)

–––, OFF, 70 to 190°F
(21 to 88°C)

35 to 100°F, OFF
(2 to 38°C)

Note: Depending on the settings the installer makes in the control, certain items may not appear.