Control menus, View menu, Adjust menu – tekmar 362 Mixing Control User Manuals User Manual
Page 2

Copyright © 1999 U 362 -06/99
2 of 4
Current outdoor air temperature as measured by the outdoor
sensor. This is also the default display for the control.
-67 to 149˚F
(-55 to 65˚C)
•
•
Target room air temperature. “— — —” denotes no heat is required.
Will not display if RTU is connected.
- - -, 35 to 100˚F
(2 to 38˚C)
Measured room air temperature at the indoor sensor.Will not display
if RTU is connected.
-58 to 167˚F
(-50 to 75˚C)
Current mixed supply water temperature as measured by the
mixing sensor.
-31 to 266˚F
(-35 to 130˚C)
•
•
•
Current operating status of the snow melting system.
STRT, STOP, IDLE, EXT,
00:0 to 17:00 hr, - - -,
INF, WWSD, CWCO
Current boiler supply water temperature as measured by the
boiler sensor.
-31 to 266˚F
(-35 to 130˚C)
•
Current boiler return water temperature as measured by the
boiler sensor.
-31 to 266˚F
(-35 to 130˚C)
•
•
•
•
Item
Range
LT
D
USER
362 View Menu
Item
Range
LT
D
USER
When operating with a slab sensor, this item is the desired slab
surface temperature while in the Melting Mode. When operating
without a slab sensor, this item is the mixing supply water temperature
while in the Melting Mode.
•
32 to 92˚F or 140˚F
(0 to 35˚C or 60
°C)
The time for which the slab is operated once it has reached the
MELTING temperature. This item cannot be viewed if a Remote Start
/ Stop Module 039 has been connected.
OFF, 0:30 to 17:00
hr
INF (Infinity)
•
•
362 Adjust Menu
Occ
35 to 100˚F
(2 to 38˚C)
The desired room air temperature during an Occupied period. In LTD
access level, this setting can only be adjusted
±3°F (±1°C).
•
•
UnOcc
35 to 100˚F
(2 to 38˚C)
The desired room air temperature during an UnOccupied period.
•
•
OFF, 35 to 120˚F
(OFF, 2 to 49˚C)
The minimum temperature at the slab sensor provided that the control
is not in Warm Weather Shut Down. This item can only be adjusted
if a tekmar sensor is connected.
0 to 50˚F
(0 to 28˚C)
•
The amount that the mixing supply temperature will be reduced when
the control is in an UnOccupied Mode.
•
35 to 100˚F, OFF
(2 to 38˚C, OFF)
Occ
The system’s warm weather shut down during the Occupied period.
Mode 1 is for Heating. Mode 2 is for Snow Melting.
Note: Depending on the settings the installer make in the control, certain menu items may not appear.