beautypg.com

Settings, Step two, Step three – tekmar 155 Difference Setpoint Control User Manual

Page 2: Step four, Programming

background image

2

Step Two

Mounting

The control is mounted in accordance with the instructions in the Data Brochure D 001.

Step Three

Rough-in wiring

All electrical wiring terminates in the two wiring chambers at the bottom front of the control. If the control is to be mounted on
an electrical box, the wiring can be roughed-in at the electrical box prior to installation of the control (see Brochure D 001).
Standard 18 AWG solid wire is recommended for all low voltage wiring to this control.

Power should not be applied to any of the wires during the rough-in wiring stage.

• Install the Source Sensor 085 and Storage Sensor 071 according to the instructions in Data Brochure D 085 and D 070, and run

the wiring back to the control. Do not connect the wires to the terminals yet.

• EITHER: Install a 24 V (ac) Class 2 transformer with a minimum 5 VA rating and run the wiring from the transformer to the control.

A Class 2 transformer must be used. Do not connect either of the transformer secondary wires to ground.
OR: Install a 24 V (dc) source and run the wiring back to the control.

• Run wiring back to the control from the devices connected to Relay 1 and Relay 2.

Step Four

Testing and connecting the wiring

Caution These tests are to be performed using standard testing practices and procedures and should only be carried out by properly

trained and experienced persons. A good quality electrical test meter, capable of reading from at least 0 — 200 Volts, and
at least 0 — 2,000,000 Ohms, is essential to properly test this control. At no time should voltages in excess of 27 V (ac or
dc) be measured at any of the wires connected to the control.

Test the sensors

• This test must be performed

before power is applied to the control and before the sensors are connected to the terminal strip.

Test the sensors according to the instructions in the enclosed Data Brochure D 085 and D 070.

Test the power supply

• Ensure exposed wires are not grounded or in contact with other wires, then turn on the power supply. If a 24 V (ac) transformer

is used, make sure the voltmeter is set to AC. With the voltmeter leads connected to the secondary side of the transformer, you
should measure between 21 and 27 V (ac). If a DC power supply is used, make sure the voltmeter is set to DC. Connect the positive
lead from the voltmeter to the positive terminal on the DC source and the negative lead from the voltmeter to the negative terminal
on the DC source. The voltmeter should measure between 21 and 27 V (dc).

• Turn off the power and complete the electrical connections to the terminal strip of the control.

Power and output connections
The installer should test to confirm that no voltage is present at any of the wires.

• EITHER: Connect the 24 V (ac) power supply to terminals

Power C- and R+ (1 and 2)

OR: Connect the negative (-) lead from the 24 V (dc) source to the Power C- terminal

Connect the positive (+) lead from the 24 V (dc) source to the Power R+ terminal

Note: The control will not operate if the DC leads are reversed.
• Connect the Relay 1 controlled device to terminals

Relay1 (3 and 4)

• Connect the Relay 2 controlled device to terminals

Relay 2 (5 and 6)

Sensor connections — Caution, voltage is never applied to these terminals

• Connect the Source Sensor 085 to terminals

Com Sen and Src Sen (7 and 8)

• Connect the Storage Sensor 071 to terminals

Com Sen and Stor Sen (7 and 9)

Do not apply

power here

24 V

power

supply

Relay 1 closes to

transfer heat

from the source

to the storage

Relay 2 closes to

satisfy drainback

or draindown

requirements

1

C-

2

R+

3

4

10A

10A

Relay 1

Relay 2

5

6

7

Com

Sen

Src

Sen

Stor

Sen

8

9

Source

Sensor

085

Storage

Sensor

071

Power

Settings

Note: The control automatically

exits programming when

the buttons are left alone

for 20 seconds.

Use the arrow

keys to set the

“ΔT Differential”.

Press and Release

the “Item” button to

change the display to

the “ΔT Differential”.

Press and Release

the “Item” button to

change the display to

the “Minimum Source

Setpoint”.

Use the arrow

keys to set the

“Minimum

Source

Setpoint”.

Press and Release

the “Item” button to

change the display to

the “Minimum Source

Differential”.

Use the arrow

keys to set the

“Minimum Source

Differential”.

Press and Release

the “Item” button to

change the display to

“°F” or “°C”.

Use the arrow

keys to switch

between “°F”

and “°C”.

Use the arrow

keys to set the

“ΔT setpoint”.

PROGRAMMING

Press and Release

all three buttons at the

same time to begin

programming. The first

item displayed is the

“ΔT setpoint”.

Press and Release

the “Item” button to

change the display to

the “Maximum Storage

Setpoint”.

Use the arrow

keys to set the

“Maximum

Storage

Setpoint”.

Press and Release

the “Item” button to

change the display to

the “Maximum Storage

Differential”.

Use the arrow

keys to set the

“Maximum

Storage

Differential”.

Diff'l

PRGM

F

ΔT

Source

Storage

Minimum

Maximum

ΔT • hours

Diff'l

PRGM

F

ΔT

Source

Storage

Minimum

Maximum

ΔT • hours

Diff'l

PRGM

F

ΔT

Source

Storage

Minimum

Maximum

ΔT • hours

Diff'l

PRGM

F

ΔT

Source

Storage

Minimum

Maximum

ΔT • hours

Diff'l

PRGM

ΔT

Source

Storage

Minimum

Maximum

ΔT • hours

F

Diff'l

PRGM

F

ΔT

Source

Storage

Minimum

Maximum

ΔT • hours

Diff'l

PRGM

F

ΔT

Source

Storage

Minimum

Maximum

ΔT • hours

Item

Item

Item

Item

Item

Item

Item

Item

Item

Item

Item

Item

Item

Item