Fusing a fitting, Notice, Equipment setup & usage instructions – Watts TRCU-M1 User Manual
Page 15: Prepare pipe for fusion, Step 1
13
Fusing a Fitting
• Always read and follow instructions and
warnings and do not use this equipment
unless you know how to operate it cor-
rectly .
• Follow and comply with all applicable
building codes, requirements, and stan-
dards .
• Always properly prepare pipe surfaces for
fusion .
• Corrosive chemicals and materials includ-
ing contamination in water can prevent
proper fusion .
• Have water tested by a professional
before performing work . Consult the
Plastic Pipe Institute for list of chemicals
that adversely affect plastic pipe .
(www .plasticpipe .org)
• Make sure pipe is free of debris and con-
taminants .
• Water inside of pipe can prevent proper
fusion . Make sure that pipe is free of
water before performing work .
• Always use new, undamaged TRITON
Fittings and Fusers that are the correct
size for the pipe you are fusing .
• Make sure that Fitting is in place and the
Fuser is properly positioned before initiat-
ing fusion .
• Always complete a full fusion cycle – do
not stop prematurely .
NOTICE
Failure to use this equipment as
instructed can result in substan-
dard pipe fusion which may fail
immediately or over time and could
cause leaking, flooding, or sub-
stantial property damage.
Equipment Setup & Usage Instructions
Prepare Pipe for Fusion
• Cut pipe cleanly and squarely using a
quality pipe cutter designed for the pipe .
• Gently wipe end of pipe with clean, dry
work towel to remove any oils or fluids .
• Remove any burrs or flash.
NOTICE
Do not use abrasive cloth or emery
paper on pipe to clean.
STEP 1