Materials list, Pressure – temperature, Typical applications – Watts 2300 User Manual
Page 2: Dimensions — weights, Capacity, Washroom water supply, Domestic water pressure control for tall buildings

Materials List
Body
CastIron
Disc
HycarComposition
Trim
Stainless Steel
Diaphragm
Hycar
Spring
Tempered Steel
Pressure – Temperature
MaximumTemperature:150°F(66°C)
MaximumPressure:200psi(13.8bar)
ReducedPressureRange:30–80psi(207–552kPa)
Typical Applications
Washroom Water Supply
Series 2300 is a direct operated, balanced, tight seating pressure
reducing valve, opened and closed by small variations in delivery
pressure.
Series 2300 provides
each floor of the building
with water at a steady
economical pressure.
The delivery pressure
acting on the spring
loaded diaphragm throt-
tles the balanced valve
to control the pressure.
Water from
StreetMain
Series 2300 Valve
Domestic water pressure control for tall buildings
C
B
E
A
Size
DiMeNSiONS
WeiGHTS
A
B
C
E
in.
in.
mm
in.
mm
in.
mm
in.
mm
lbs.
kgs.
3
6
153
21
3
⁄
4
552
9
229
10
254
108
49
4
6
5
⁄
8
168
26
5
⁄
8
676
11
1
⁄
4
286
11
7
⁄
8
302
198
90
Dimensions — Weights
0 100 200 300 400 500 600 700 800 900
gpm
0 380 760 1140 1520 1900 2280 2660 3040
3420
lpm
Flow
kPa psi
0 0
34 5
103 15
138 20
172 25
207 30
241 35
276 40
Reduced Pressure Drop
3"
4"
Capacity
To Building Services
To Building Services
To Building Services
From City Main
Series
2300
Series
2300
Series
2300
ES-23001410
©2014Watts
USA:Tel:(978)688-1811•Fax:(978)794-1848•www.watts.com
Canada: Tel:(905)332-4090•Fax:(905)332-7068•www.watts.ca
A Watts Water Technologies Company