High capacity water pressure reducing valves, Sizes, 15 – 65mm)

background image

Series 223, 223-S

High Capacity Water Pressure

Reducing Valves*

Sizes:

1

2

" – 2

1

2

" (15 – 65mm)

Series 223 and 223-S High Capacity Water Pressure Reducing

Valves are designed to reduce incoming water pressure to a

sensible level to protect plumbing system components and

reduce water consumption. This series is suitable for water sup-

ply pressures up to 300psi (20.7 bar) and may be adjusted from

25 – 75psi (172 – 517 kPa). The standard setting is 50psi (345

kPa). Series 223 features an enlarged diaphragm, spring cage

and seat orifice for high capacity performance. Series 223-S

has the same options as the 223, except it is furnished with

a strainer. All parts are quickly and easily serviceable without

removing the valve from the line. The optional bypass feature

permits the flow of water back through the valve into the main

when pressures, due to thermal expansion on the outlet side of

the valve, exceed the pressure in the main supply.

Features

•   Enlarged diaphragm, spring cage and seat orifice for super 

capacity performance

•   Bronze body construction (except 2

1

2

" (65mm) which is iron)

•   Serviceable in line
•   Series 223-S furnished with separate strainer
•   Optional bypass feature controls thermal expansion pressure**
•   Sealed spring cage on all models for accessible outdoor or 

pit installations.

Models

223

NPT threaded female inlet x NPT threaded female outlet

223-S NPT threaded female inlet with strainer x NPT threaded

female outlet

For 2

1

2

" – 3" (65 – 80mm) bronze threaded valves, refer to 

literature ES-N223B.
For 3" (80mm) flanged connections, refer to literature ES-N223F.

Specifications

A Water Pressure Reducing Valve shall be installed on the

water service pipe near its entrance to the building where

supply main pressure exceeds 60psi (413 kPa) to reduce it to

50psi (345 kPa) or lower. Sill cocks and outside wall hydrants

may be left on full main pressure at the option of the owner.

Provision shall be made to permit the bypass flow of water

back through the valve into the main when pressures, due to

thermal expansion on the outlet side of the valve, exceed the

pressure in the main supply. Pressure reducing valves with

built-in bypass check valves and strainer will be acceptable.

Approved valves shall comply with ASSE 1003. Valve shall be 

a Watts Series 223 or 223-S (with strainer).

For Commercial, Institutional and Industrial Applications

ES-223

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer   ––––––––––––––––––––––––––––––––––––––––––––– 

Contractor’s P.O. No.   ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Available with or without

separate strainer

223-S

Disc holder removable for replacement of

disc without dismantling the valve —

no special tools required.

Sensitive spring

and large dia-

phragm area for

accurate

pressure control

Bronze body

construction

1

2

" – 2"

Replaceable

stainless seat

High temperature

resisting diaphragm

for hot or cold water.

Large stainless steel

perforated strainer screen.

Sealed spring cage

* A water saving test program concluded that reducing the supply pressure from

80-50psi (551-345 kPa) resulted in a water savings of 30%.

** The bypass feature will not prevent the pressure relief valve from opening on

the hot water supply system with pressure above 150psi (10.3 bar).

IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES

FOR LOCAL INSTALLATION REQUIREMENTS

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.