U-gage, S18u series sensor — analog output, Teaching limits using the auto-window feature – Banner U-GAGE S18U Series—Analog User Manual
Page 5

P/N 110738 rev. A
5
U-GAGE
™
S18U Series Sensor — Analog Output
Banner Engineering Corp.
•
Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
Procedure
Result
Push Button
0.04 < “click” < 0.8 sec.
Remote Wire
0.04 sec. < T < 0.8 sec.
Programming
Mode
• Push and hold the
push button
• No action required; sensor is ready for
first limit teach
Output LED: ON Red
Power LED: ON Green (good signal) or
ON Red (no signal)
Teach
Limit
• Position the target for
the center of the window
• Position the target for the center of the
window
Power LED: Must be ON Green
• “Click” the push button
• Single-pulse the remote line
Teach Accepted
Output LED: Flashing Red
Teach Unacceptable
Output LED: ON Red
Re-T
each
Limit
• Without moving the
target, “click” the
push button again
• Without moving the target,
single-pulse the remote line
again
Teach Accepted
Output LED: Yellow or OFF
Teach Unacceptable
Output LED: Flashing Red
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
...
...
D
or
...
...
D
or
...
...
D
or
Teaching Limits Using the Auto-Window Feature
Teaching the same limit twice for the same output automatically centers a 100 mm
window on the taught position.
General Notes on Programming
• The sensor will return to Run mode if the first Teach condition is not registered
within 120 seconds.
• After the first limit is taught, the sensor will remain in Program mode until the Teach
sequence is finished.
• To exit Program mode without saving any changes, press and hold the programming
push button > 2 seconds (before teaching the second limit). The sensor will revert to
the last saved limits.
• Using this procedure the analog output will be centered on the taught position at
approximately 5V dc or 12 mA.
B