beautypg.com

Planning the cable run in the apartment – CommScope Drop Cable User Manual

Page 49

background image

Planning the Cable Run in the Apartment

Customer needs dictate where the outlets are located. Visually inspect every proposed outlet location. Be aware

of potential problems like electrical outlets or HVAC ducting. You may not have the ability to drop cable from an

attic or run up from a crawlspace, so your routing options may be limited. The preferred method would be to fol-

low telecommunication conduit (if it exists) into the building. If not, consider the options shown below.

From the Outside

In the example floor plan, there are two ways to bring the cable in. The solid line shows running the cable from

the exterior, entering the wall and running to the two locations. A suggested routing would be to bring the out-

door cable in at the ceiling line, run the cable along the top of the wall and split it there. Use methods described

on page 9.4 to position the entry point correctly. You can run non-rated cables a maximum of 50 feet (15 meters)

into an MDU; any further distance requires a CATV-rated cable. A CATV-rated cable is then either fished through

or attached to the wall and concealed with wiremold to reach the outlet location. See Section 9 for specifics. The

cable then continues along the top of the wall, over the door and through the interior wall to the second outlet,

where it is either fished or attached to the wall and

hidden with wiremold.

From the Inside

The dotted line shows a possible route from an inte-

rior hallway. Cable from a riser is run along the top

of the hall wall and enters the apartment at the ceil-

ing. Use methods described in section 9 to position

the entry point correctly. The cable is split and either

fished through the wall or attached to the outside of

the wall. The cable continues along the top of the

wall, over the door and around to the second outlet,

where it is fished or run down to the outlet location.

Multiple Dwelling Units (MDUs) 10.2

Planning and Pulling the Cable