beautypg.com

Overview – CommScope Drop Cable User Manual

Page 48

background image

Overview

Multiple Dwelling Units (MDUs) have a more strict set of rules for cable installation than single family residences.

Service is dropped from the tap to the building like a residential installation, either aerially (see Section 6) or un-

derground (see Section 7). However, the cable is usually run to some sort of interconnect box which allows the

service provider to secure the connection and prevent tampering. This box may be inside or outside the building.

A building with two or more apartments or condominiums is not considered to be a

single-family residence and is governed by commercial building and safety regulations.

For instance, you may need to use riser-rated cables instead of CATV rated residential

cables. A general rule of thumb is if the cable penetrates the floor (if it runs vertically

between floors), then you must use a riser-rated cble (CATVR for coax, CMR for UTP,

OFNR for fiber). The riser cable is then run horizontally to the outlet (while you may use

a lower rated cable for horizontal runs, the extra time and cost of termination outweighs

the cost difference between the cables). You may use CATV cable inside metal conduit to

pass between floors, though using a riser-rated cable is much easier.

Signal Amplification

Another issue to consider is amplification. The signal being carried by the drop could be split literally dozens of

times, thus decreasing its strength to the point where it is no longer viable. This is solved by installing a line ampli-

fier before the crossconnection. While most amplifiers are powered by the voltage in the cable, some require con-

nection to 110/120V power. Consult the directions from the manufacturer for specific powering instructions.

The run from the crossconnect to the apartment could be several hundred feet. You may wish to consider upgrad-

ing your cable (example: from F11 to QR 320) or installing another line amplifier along the route.

Article 830 Considerations

The same rules apply concerning aerial distances (page 5.1), burial depth (page 6.1) and use of raceway or

conduit within 8 ft (2.5 m) of the ground as residential installation. Article 830 also permits you to transition up to

50 ft (15.2) meters of cable to meet an interior-mounted NIU. Longer runs require that the cable be run in metal

conduit or within the wall like electrical wiring.

tech tip:

review

section 9

for complete

advice on

running

cables inside

a structure

10.1 Multiple Dwelling Units (MDUs)

Overview