Rockwell Automation FlexPak 3000 Drive Field Current Regulator Kit, 911FK0041, 911FK0101, 911FK015 User Manual
Page 33
Modifying the Drive Configuration
5-3
Step 17. Turn on power to the drive.
Step 18. Access the Fault menu by pressing the FAULT key until FAULT appears on
the OIM directly above the FAULT key.
Step 19. Select Clear Fault Log and Reset Faults, and then press ENTER. The fault
log will be cleared and all drive faults will be reset. If you have an OIM, you
are done with setting parameter 510. Go to section 5.1 to set parameter 511
(
FIELD
ECONOMY
REF
).
Important: Performing a Restore Defaults operation will cause the Field Current
Regulator to re-enter the fixed voltage mode of operation and require the
re-execution of the above steps.
If the drive is equipped with a DCM, use the following steps to set MOTOR HOT
FLD AMPS.
Step 20. From the main menu, scroll to Input Parameters and press ENTER.
Step 21. Scroll to
HOT
FLD
AMPS
.
Step 22. Set
HOT
FLD
AMPS
to the value printed on the motor nameplate.
Step 23. From the main menu, scroll to Memory Operations and press ENTER.
Step 24. Scroll to Memory Save, and then perform the memory save operation.
If the motor field winding was disconnected in step 2 above, perform steps
25-29. Otherwise, proceed to step 30.
Step 25. Disconnect, tag, and lockout power to the drive.
Step 26. Reconnect the motor field winding to the drive.
Step 27. Reconnect power to the drive
Step 28. Remove the lockout and tag.
Step 29. Turn on power the drive.
Step 30. Access the Fault menu and press ENTER.
Step 31. Scroll to Clear Fault Log and Reset Faults, and then press ENTER. The fault
log will be cleared and all drive faults will be reset.
Important: Performing a Restore Defaults operation will cause the Field Current
Regulator to re-enter the fixed voltage mode of operation and require the
re-execution of the above steps.