Safety considerations, Specifications – Rockwell Automation T3122 ICS Regent Processor Modules User Manual
Page 18

Processor Modules (T3110, 11, 12, 20, 21, and 22)
1 8
Industrial Control Services
Safety Considerations
Processor module catalog numbers T3110, T3112, T3120 and
T3122 are TÜV certified for Risk Class 5 safety critical
applications. Catalog numbers T3111 and T3121 (220 VAC
powered modules) have not been certified as they do not meet
the DIN VDE 0110 requirements for creepage and clearances.
Specifications
Voltage Range
T3110/T3120:
T3111/T3121:
T3112/T3122:
85 to 132 VAC
170 to 263 VAC
20 to 30 VDC
Frequency Range
T3110/T3120:
T3111/T3121:
T3112/T3122:
47 to 63 Hz
47 to 63 Hz
—
Maximum Load
100 VA
Fusing
2 A, 250 V, slo blo (3AG),
(located on controller chassis)
Use with Chassis
T3110/T3120:
T3111/T3121:
T3112/T3122:
T3100
T3101
T3102
Power Hold-Up Time
10 msec, minimum
Heat Dissipation
46 Watts, 156 BTUs/hour
Fault Contact Rating
(Class II Connection Only)
Load Current (max.):
Load (min.):
Voltage (max.):
Switching Capacity
(max.):
1 amp
10 mV, 0.1 mA
30 VAC, 42.5 VDC
30 VA, 42.5 VAC (resistive)