3.10. I/O Complex Equipment Definition T8310
Each module fitted in a Trusted
TM
system requires an entry in the I/O Connection table, specifying its
chassis and slot number. The I/O Complex Equipment Definition allows control of the module’s
functions, and provides information on its status. For information on editing the I/O Connection table,
refer to PD-8082B. The definition for this module is described below.
OEM PARAMETERS
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
2 – 15
13 and 14 (Expander Chassis)
The TICS chassis & slot number where the T8310 module
is placed. Expander processor modules cannot be placed
in a processor chassis.
By definition, the primary module is placed in the left-hand
slot (13) and the secondary in the right-hand slot (14).
CONFIGURATION
PHYSICAL MODULE:
RACK 1: [XPM_0]
16 ANALOGUE
inputs
Channel 1: Not used
Channel 2: 24V dc Feed 1
Channel 3: 24V dc Feed 2
Channel 4: Not used
Channel 5: Not used
Channel 6: Not used
Channel 7: Slice A Rx error count
Channel 8: Slice B Rx error count
Channel 9: Slice C Rx error count
Channels 10 to 16 – Not used.
RACK 2: (INFO)
11 INTEGER inputs
Channel 1:Chassis position of AM
Channel 2:Slot position of AM
Channel 3:Indication of global health of AM
1 – No slice errors and module is responding
0 – Some error has been found
Channel 4:Current state of AM
Channel 5:Chassis position of SM
0 – No partner exists
Channel 6:Slot position of SM
0 – No partner exists
Channel 7:Indication of global health of SM
1 – No slice errors and module is responding
0 – Some error has been found
Channel 8:Current state of SM
Channel 9:Slice information of SM. See Note
Channel 10
Is AM the Primary Module
1 – Yes 0 – Not
Channel 11:Not used