Module indicators – Rockwell Automation 1440-SPD02-01RB XM-220 Dual Speed Module User Manual
Page 7
Rockwell Automation Publication ENMON-IN220D-EN-P - February 2014
7
XM-220 Dual Speed Module
Module Indicators
The XM-220 module has seven status indicators, which are on top of the module.
Module Status (MS) Indicator
Network Status (NS) Indicator
1
TIP
The AUX indicator is reserved for future use.
Color
State
Description
No color
Off
No power applied to the module.
Green
Flashing red
Module performing power-up self-test.
Flashing
Module operating in Program mode.
(1)
(1) Program mode - Typically this occurs when the module configuration settings are being updated with the XM Serial Configuration Utility. In Program mode, the module does not perform its normal
functions. The signal processing/measurement process is stopped, and the status of the alarms is set to the disarm state to prevent a false alert or danger status.
Solid
Module operating in Run mode.
(2)
(2) Run mode - In Run mode, the module collects measurement data and monitors each measurement device.
Red
Flashing
• Application firmware is invalid or not loaded. Download firmware to the module.
• Firmware download is currently in progress.
Solid
An unrecoverable fault has occurred. It is possible that the module must be repaired or replaced.
Color
State
Description
No color
Off
Module is not online:
• Module is autobauding.
• No power applied to the module; look at Module Status indicator.
Green
Flashing
Module is online (DeviceNet network) but no connections are currently established.
(1)
(1) Normal operation when the module is not a slave to an XM-220, programmable controller, or other master device.
Solid
Module is online with connections currently established.
Red
Flashing
One or more I/O connections are in the timed-out-state.
Solid
Failed communication (duplicate MAC ID or bus-off).
DUAL SPEED
1440-SPD02-01RB
Module Indicators