2 module diagnostic items – Rockwell Automation RECOMM-485 RS485 DFI Communications Module User Manual
Page 39

Troubleshooting the Module and Network
6-5
6.1.4 NET B Status Indicator
6.2
Module Diagnostic Items
Table 6.5 lists diagnostic items that can be accessed using
VS Utilities software or the LCD OIM.
Table 6.4 – NET B Status Indicator: State Definitions
Status
Cause
Corrective Actions
Off
The module is not
receiving data over
the network.
•
Place the controller in RUN, or
apply power to the peer device
that will send I/O.
•
Program a controller peer
device to recognize and
transmit I/O to the module.
•
Configure the module for the
program in the controller or the
I/O from the peer device.
Flashing
Green
The module is
receiving data over
the network.
•
No action required.
Table 6.5 – Module Diagnostic Items
No.
Event
Description
1
Common Logic
Cmd
The current value of the Common Logic
Command being transmitted to the host by this
peripheral.
2
Prod Logic Cmd
The current value of the Product Specific Logic
Command being transmitted to the host by this
peripheral.
3
Reference
The current value of the Product Specific
Reference being transmitted to the host by the
peripheral.
4
Common Logic Sts The current value of the Common Logic Status
being received from the host by this peripheral.
5
Product Logic
Status
The current value of the Product Specific Status
being received from the host by this peripheral.
6
Feedback
The current value of the Product Specific
Feedback being received from the host by this
peripheral.