beautypg.com

Triguard sc300e environmental specifications, Transport and handling – Rockwell Automation MPP Processor Moduile User Manual

Page 4

background image

4

MPP October 2005 – Issue 6

Triguard SC300E

Environmental specifications

The maximum ambient temperature measured at the hottest point within the Triguard system
shall not be greater than 60 degrees centigrade.

Temperature operating:

+5°C to 60°C

Temperature storage:

-25°C to +70°C

Humidity

5% to 95% non-condensing at ambient <40°C

EMC/RFI Immunity

Tested and certified to IEC 1131-Part 2 1994

Vibration/Shock

Tested and certified to IEC 1131-Part 2 1994

Certification:

General Certification: Ref. SC300E Product Guide (ref 008-5209)

TRANSPORT AND HANDLING

The processor module must be transported and stored in its original packing material which
should be retained for this purpose.