Rack 7: hkeeping, Table 12 rack 7: housekeeping descriptions, Trusted – Rockwell Automation T8461 Trusted TMR 24 48Vdc Digital Output Module User Manual
Page 22: Module t8461
Trusted
TM
Module T8461
Issue 13 Apr 10
PD-T8461
22
3.2.7. Rack 7: HKEEPING
Description
Channel
FCR
Units (Full Scale Range)
1
A
2
B
3
C
24V2 Output Voltage
-32768
32767
mV
4
A
5
B
6
C
Internal supply voltage (post regulator)
-32768
32767
mV
7
A
8
B
9
C
Internal supply current (post regulator)
-32768
32767
mA
10
A
11
B
12
C
Output voltage (post isolation)
-32768
32767
mV
13
A
14
B
15
C
24V1 Output Voltage
-32768
32767
mV
16
A
17
B
18
C
HIU Board Temperature
( Note: Temperature, ºC = input value / 256 )
-32768
32767
-
19
A
20
B
21
C
Front Panel Load Current
-32768
32767
mA
22
A
23
B
24
C
SmartSlot Link Voltage
-32768
32767
mV
25
A
26
B
27
C
FIU Output Group 1 Field Supply Voltage
-32768
32767
1/500V
28
A
29
B
30
C
FIU Board Temperature, Output Group 1
( Note: Temperature, ºC = input value / 256 )
-32768
32767
-
31
A
32
B
33
C
FIU Output Group 2 Field Supply Voltage
-32768
32767
1/500V
34
A
35
B
36
C
FIU Board Temperature, Output Group 2
( Note: Temperature, ºC = input value / 256 )
-32768
32767
-
37
A
38
B
39
C
FIU Output Group 3 Field Supply Voltage
-32768
32767
1/500V
40
A
41
B
42
C
FIU Board Temperature, Output Group 3
( Note: Temperature, ºC = input value / 256 )
-32768
32767
-
43
A
44
B
45
C
FIU Output Group 4 Field Supply Voltage
-32768
32767
1/500V
46
A
47
B
48
C
FIU Board Temperature, Output Group 4
( Note: Temperature, ºC = input value / 256 )
-32768
32767
-
49
A
50
B
51
C
FIU Output Group 5 Field Supply Voltage
-32768
32767
1/500V
52
A
53
B
54
C
FIU Board Temperature, Output Group 5
( Note: Temperature, ºC = input value / 256 )
-32768
32767
-
55
A
56
B
57
C
Diagnostic error code
Table 12 Rack 7: Housekeeping descriptions