Step 4: Removing the Control
Frame and Conduit
Task
Description
If removing a Control Frame from a DC input drive with precharge interlock, disconnect the wiring from
terminal strip X50.
Remove the eight M4x8 Pozidrive screws, which secure the Control Frame to the drive.
Proper tightening torque for reassembly is 3 N•m (27 lb•in).
Remove the six M4x8 Pozidrive screws, which secure the Conduit to the drive.
Proper tightening torque for reassembly is 3 N•m (27 lb•in).
Remove the Conduit from the drive.
Remove the Control Frame from the drive while carefully routing the cables and wires through the access
hole of the Control Frame.
IMPORTANT
Before removing connections and wires, mark the connections and wires to
avoid incorrect wiring during assembly.
A
B
C
D
E
Control Frame
Conduit