A-4
LiquiFlo AC Power Modules, Hardware Reference Version 6.4
*These are the maximum times from transitioning the input to the drive reacting to the input.
Table A.7 – Input Signal Response Times (Maximum)
Signal Type and Source
Volts/Hertz Regulation*
Vector Regulation*
Keypad START
150 milliseconds
130 milliseconds
Terminal Strip:
START
126 milliseconds
105 milliseconds
STOP, RESET, FL
75 milliseconds
75 milliseconds
Preset Speeds
75 milliseconds
75 milliseconds
Analog Speed/Trim
Reference
16 milliseconds
5 milliseconds
Analog Torque
Reference
N/A
0.5 milliseconds
Network:
START
46 milliseconds +
network transport time
25 milliseconds +
network transport time
STOP, RESET, FL
26 milliseconds +
network transport time
25 milliseconds +
network transport time
Analog Speed/Trim
Reference
5 milliseconds +
network transport time
5 milliseconds +
network transport time
Torque Reference
N/A
0.5 milliseconds +
network transport time
Motor Overload Protection
Electronic Motor
Overload Protection
Provides class 10 motor overload protection according
to NEC article 430. Does not provide speed sensitive
overload protection, thermal memory retention, and
motor over-temperature sensing according to NEC
article 430.126 (A) (2). If such protection is needed in
the end-use product, it must be provided by additional
means.