Rockwell Automation SP200 Input Mains Filter Model Number S20-MF1-Y014, S20-MF1-45P0, S20-MF1-49P5 User Manual
Input mains filter
![background image](/manuals/581514/1/background.png)
INPUT MAINS FILTER
(Model Number: S20-MF1-Y014, S20-MF1-45P0, S20-MF1-49P5)
INSTALLATION
ATTENTION: The input mains filter connects between the incoming AC supply line and
the drive input terminals. The filter must be installed by qualified personnel familiar with the
drive and associated machinery. Failure to comply may result in personal injury and/or
equipment damage.
ATTENTION:
An incorrectly applied or installed input mains filter can result in component
damage or a reduction in product lifeWirirng or applicationn errors, such as incorrect wiring
layout, incorrect or inadequate AC supply or excessive ambient temperature may result in
malfunction of the system
ATTENTION:
To prevent electrical shock, disconnect from power before installing or
servicing. High leakage current, connect to earth.
1. Mount the input mains filter to the panel. Refer to the dimensions drawing shown
on the next page.
2. Using the picture beside as a guide, mount the drive to the filter.
Side by side mounting is also possible where enclosure depth is limited
3. The input mains filter should be connected between the incoming AC supply
and the drive input terminals
Important: The three phase filter may cause groung leakage currents.
Therefore a solid ground connection must be provided
4. Connect remaining wires.
5. To assure that the input mains filter is effective follow the general installation
guidelines as discribed in the SP200 AC Drive Quick Start Guide (D2-3418-1)
Input Mains Filter
Module
Rated Voltage /
Rated Current
To Be Used with
SP200 AC Drive Model:
S20-MF1-Y014
1~ / 200-240V / 14A
S20-X02P3_1000
S20-X04P2_1000
S20-X06P0_1000
S20-Y07P0_1000
S20-MF1-45P0
3~ / 200-460V / 5A
S20-202P3_1000
S20-204P2_1000
S20-401P3_1000
S20-402P0_1000
S20-402P3_1000
S20-MF1-49P0
3~ / 200-460V 9A
S20-207P0_1000