INSTALLATION

WARNING

BEFORE ATTEMPTING TO INSTALL THE MINĆ

PAK PLUS MODIFICATION KIT, DISCONNECT

AND LOCK OUT ALL SOURCES OF INCOMING

POWER TO THE CONTROLLER.

1. Locate the area on the Regulator Module where the

Remote Operator Adapter Module is to be

mounted. Place the Module in the proper orientaĆ

tion: the edge with 10 holes should be aligned over

the 10 pins. (Refer to Figure 2). Carefully, slowly

and gently press the Module down on the pins

until it bottoms out. Use the 2 screws to secure

it.

2. Based on the specific control capability of the ReĆ

mote Operator Station chosen, select the required

wires specified in Table 7.B, DĆ3937.

3. Draw the wires into the Controller through the dediĆ

cated conduit. Then cut individual wires to lengths

required for connection to the kit's terminal strip.

Wire according to Figure 3.4, DĆ3937.

WARNING

EXCESSIVE LENGTHS OF BARE WIRE COULD

CAUSE SHORTS AND/OR GROUNDS. STRIP

MINIMAL INSULATION FROM EACH WIRE.

4. Visually inspect all wiring. Check wire placement

against diagrams. Look for grounds and shorts

caused by broken insulation. Make sure the conduit

is grounded.

5. Attach the blank faceplate onto the cover if not alĆ

ready supplied. Follow installation instructions proĆ

vided in Instruction Manual DĆ3977 MinPak Plus loĆ

cal operator station faceplate. Be sure to attach

ground wire to cabinet door.

DANGER

IT IS NECESSARY TO ATTACH THE FACTORY

CONTROLLER GROUND WIRE TO THE CONĆ

TROLLER CABINET DOOR VIA THE LOCAL

OPERATORS STATION FACEPLATE. PERĆ

SONAL INJURY MAY RESULT IF THIS PRACĆ

TICE IS NOT FOLLOWED.

35> When remote operator buffer kit is used with

switch receiver kit auto/manual switch is conĆ

nected to 326126 and 26 (instead of 326 426 and

POT wiper) on the remote operator butter kit terĆ

minal board. The respective pins mate with NC

232 and 32 on the switch receiver kit.

36 > If NOT using an auto/manual switch for automatic

operation only jumper terminals 426 and 326.

PRINTED CIRCUIT BOARD

NOT ARRANGED IN

ORDER SHOWN.

Figure 3 - Remote Operator Adapter Kit Schematic Diagram