Rockwell Automation T3431-CA ICS Regent Thermo Couple Input Assembly User Manual
Page 26
![background image](/manuals/581443/26/background.png)
Thermocouple Input Assembly (T3431)
2 6
Industrial Control Services
Thermocouple Accuracy
Maximum error (0
°
to 60
°
C).
Add ±0.5 LSB resolution error to
the following:
Type J, Full range:
Type K
< -100
°
C:
> -100
°
C:
Type S
< 540
°
C:
> 540
°
C:
Type T
< 0
°
C:
> 0
°
C:
±1.6
°
C (3.0
°
F)
±4.2
°
C (7.6
°
F)
±2.4
°
C (4.3
°
F)
±13
°
C (24
°
F)
±7
°
C (12.5
°
F)
±4.8
°
C (8.7
°
F)
±2.1
°
C (3.8
°
F)
Wire Resistance Effects
Type J, Full range:
Type K
< -100
°
C:
> -100
°
C:
Type S
< 540
°
C:
> 540
°
C:
Type T
< 0
°
C:
> 0
°
C:
-0.0020
°
C/ohm (.0036
°
F)
-0.0066
°
C/ohm (0.0120
°
F)
-0.0033
°
C/ohm (0.0060
°
F)
-0.0200
°
C/ohm (0.0360
°
F)
-0.0100
°
C/ohm (0.0180
°
F)
-0.0066
°
C/ohm (0.0120
°
F)
-0.0025
°
C/ohm (0.0045
°
F)
Adjacent Channel Effects
Channel n = top of range
channel; n-1 = bottom of range
Type J:
Type K:
Type S:
Type T:
-1.0
°
C (1.7
°
F)
-1.5
°
C (2.7
°
F)
-4.0
°
C (7.2
°
F)
-0.8
°
C (1.5
°
F)
Channel n = bottom of range; n-1
= open circuit
Type J:
Type K:
Type S:
Type T:
-3.0
°
C (5.4
°
F)
-4.0
°
C (7.2
°
F)
-30
°
C (54
°
F)
-4.5
°
C (8.1
°
F)