Monitored Digital Input Modules (T7411)


1 6

Industrial Control Services

inputs with the standard (T0412 and T0413) line monitor
devices installed. If non-standard line monitor devices are
installed, then the threshold values may need to be
adjusted.

3) Edit each point:

Choose Edit from the Module Definition dialog box to
define a name and description for each input point. In the
Line Monitored Input Point dialog, enter names and
values for the configuration fields as described below.

Figure 11. Defining a Monitored Digital Input Point.

Name

Also called the tag name, this is the name used in the
application program to reference the field input switch’s
On/Off state. The name can be up to 12 characters long.

Description

This 40-character field provides a place to describe the input
point definition. The description is used to help document
your system (it does not affect application program operation).

Fault Name

This is the name used in the application program to reference
the input point line fault status. The name can be up to 12
characters long.