Monitored Digital Input Modules (T7411)


1 2

Industrial Control Services

Figure 7. Line Monitoring, Single Switch Connected to

Redundant Modules.

With the line monitor device installed, the input voltage, Vin,
has four possible states as represented in Table 1. When the
input module reads the input, the reference voltage, Vref, is
set to the values shown in Table 1 to detect the state of the
field input and wiring.

Table 1. Input States and Reference Voltage Thresholds.

Vref

Threshold

Voltage

Vin with Line

Monitor

Vin without

Line Monitor

Stuck-on Test

32 Vdc

24 Vdc

Wire Open

Switch Open

Open Circuit

20 Vdc

16 Vdc

Switch Open

NA

On/Off

12 Vdc

8 Vdc

Switch Closed

NA

Short Circuit

4 Vdc

0 Vdc

Wire Short

Switch Closed

Stuck-Off Test

-5 Vdc