Rockwell Automation 1440-VDRP06-00RH XM-162 Direct Vibration Modules User Manual
Page 10
10
Rockwell Automation Publication GMSI10-IN026C-EN-P - February 2014
XM-160, XM-161, and XM-162 Direct Vibration Modules
Emissions
CISPR 11 (IEC 61000-6-4)
Class A
ESD immunity
IEC 61000-4-2
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±2 kV at 5 kHz on shielded power ports
±2 kV at 5 kHz on shielded signal ports
±2 kV at 5 kHz on XMbus port
Surge transient immunity
IEC 61000-4-5
±2 kV line-earth(CM) on shielded power ports
±2kV line-earth(CM) on shielded signal ports
±2kV line-earth(CM) on XMbus port
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Enclosure type rating
None (open-style)
Voltagesranges
XM-160/XM-162 Supply:
24V DC, 0.19 A
XM-161 Supply:
24V DC, 0.31 A
Power dissipation
XM160/XM-162: 4.6 W @ 24V DC (4.3 W @ 18V DC, 4.9 W @ 32V DC), Class 2/SELV
XM-161: 7.4 W @ 24V DC (7 W @ 18V DC, 8 W @ 32V DC), Class 2/SELV
External over-current protection
440-5AFUSEKIT for SELV/PELV power source
Isolation voltage
Not rated
Wiring category
(1)
2 - on shielded power and shielded signal ports
3 - on Serial ports
2 - on XMbus ports
Wire type
Power and signal connections: shielded
North American temp code
T4
IEC temp code
T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publicat
Attribute XM-16X