beautypg.com

Specifications – Rockwell Automation 1440-ACNR XM ControlNet Adapter User Manual

Page 19

background image

XM ControlNet Adapter 19

Publication

ICM-IN001B-EN-P - March 2013

Specifications

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

XM ControlNet Adapter - 1440-ACNR

Attribute

Value

Enclosure Type Rating

None (open-style)

Input Voltage

24V DC
Current Draw Max 120 mA

XM Bus Output

24V DC, 3 A Max

Isolation Voltage

50V (continuous), Basic Insulation Type
Type tested at 900V AC for 60 s, between
ControlNet to system and ControlNet to
power.

Wire Size

Power connections:

0.34... 2.1 mm

2

(22...14 AWG) solid or

stranded copper wire rated at 75 °C (167
°F) or greater 1.2 mm (3/64 in.) insulation
max, recommended strip length 8 mm
(0.31 in.)

Wiring Category

(1)

1 - on power ports
2 - on communications ports

Terminal Block Torque

0.8 N•m (7 lb•in.)

North American Temp Code

T4A

IEC Temp Code

T4