Chapter 5 - specifications – Rockwell Automation T6050 SurgeGard Incipient Surge-Conditioning Module User Manual
Page 23
![background image](/manuals/581063/23/background.png)
T6050 Hardware & Installation Guide
Chapter 5 – Specifications
PD-6050 Dec 04
13
Chapter 5 - Specifications
Analog Input
Signal Types
-10 - +10 V, 0-5 or 1-5 VDC; 0-20 or 4-20 mA
(with jumper installed across terminals 3 and 4)
Input Frequency
0-20 Hz
Isolation
+/- 15 VDC continuous
Common Mode Rejection
80 db min at 60 Hz peak input; +/- 10 VDC max
Maximum Input Voltage Range
+/- 10 VDC operating, non-destructive
Transmitter Type
2- or 4-wire; transmitter excitation supplied from external source
Input Filtering
differential input band pass (1Hz to 10Hz) amplifier/filter,
A low pass filter (10Hz), absolute-value, peak detector
Analog Output
Signal Type
4-20 mA two-wire loop powered
Load Resistance
<600 ohms
Accuracy
+/- 2 % of full scale
Ripple
± 100 mV maximum
Power Source
22-32 VDC loop powered externally supplied
Analog AC Signal Output
Signal Type
Filtered, Amplified AC Signal; 0-7 V peak-to-peak, based upon
Analog Input Amplitude, Frequency and Gain Setting
Power Requirements
Loop Powered
22-32 VDC two-wire loop powered through Analog Output
Current Requirements
45 mA surge maximum at power up, 2 mA + Analog Output
Value (20 mA maximum) equals 22 mA maximum after power
up
Power Requirements
1.44 watts surge maximum at power up, 0.7 watts maximum
after power up