Trusted

TM

AN-T80009 Trusted

TM

Intelligent Online Updates

Issue 4 Nov 08

AN-T80009

17

1.10.6.

Summary

Table 1 summarizes the differences between Normal and Intelligent Updates.

N

or

m

al

U

pd

at

e

In

te

lli

ge

nt

U

pd

at

e

Add global internal variable

Yes

Add local internal variable

Yes

Add IO variable

Yes(1)

Add function block instance

Yes

Delete global internal variable

Yes

Delete local internal variable

Yes

Delete IO variable

Yes

Delete function block instance

Yes

Change variable's name

Yes(2)

Change variable's initial value

Yes(3)

Yes

Change variable's direction (internal, input, output)

Yes

Change variable's retain setting

Yes(4)

Yes(4)

Change variable's Modbus address

Yes

Yes

Change variable's comment

Yes

Yes

Add a program

Yes

Add a function

Yes

Yes

Add a function block

Yes

Delete a program

Yes

Delete a function

Yes

Delete a function block

Yes

Change the code of a program

·

Yes

Change the code of a function

·

Yes

Change the code of a function block

Yes

Change the order of programs

Yes

Change the parameters of a function

Yes

Yes

Change the parameters of a function block

Yes(5)

Change the local variables of a function block

Yes

Add a conversion table

Yes

Delete a conversion table

Yes

Change the contents of a conversion table

Yes

Yes

Remove, assign, or change a variable’s conversion table

Yes

1 - Yes, but must connect to existing, unallocated I/O point.
2 - Yes, but variable will not maintain value across update.
3 - Yes, but only if initial value has already been specified.
4 - Yes, but previously retained values will not be available.
5 - Yes, but will not maintain internal value across update.

Table 1 Intelligent Update Summary