6. Specifications
System Supply Voltage Range
20 to 32V dc
Number of Inputs
40 Channels
User Defined Thresholds
4-off
Input Current Range
0-22mA
Input Voltage Range
0-6 Vdc
Sample Update Time
0.5ms
Resolution
3.9uA (1/256mA)
Safety Accuracy
+/- 1% of full scale
(default threshold above which 0x70nn series slice discrepancy faults are raised)
Calibration Accuracy
0.03%
Recommended input channel calibration check
interval
2 years
Circuit Type
Fault tolerant, fully triplicated with
optional line monitoring
Fusing
None, external if required
Intrinsic Safety
External barrier
Sequence of Events
Event Resolution
Time-stamp Accuracy
1ms
±0.5 ms
Field Common Isolation
Sustained Working
Maximum Withstanding
±250V dc
±2.5kV dc
Channel to Channel Crosstalk
-40 to –60 dB
Power Consumption
15 – 18W
Self-Test Interval
2 minutes
Operating Temperature
-5
°C to 60°C (23°F to 140°F)
Non-operating Temperature
-25
°C to 70°C (-13°F to 158°F)
Temperature change
0.5ºC/min
Operating Humidity
10 – 95% RH non-condensing
Environmental Specifications
Refer to Document 552517
Dimensions
Height
Width
Depth
266mm (10.5ins)
31mm (1.2ins)
303mm (12ins)
Weight
1.149kg (2.5lbs)
Real Time Clock Resolution
100
µSec