3.2.2. Rack 2: STATE

This board provides the majority voted numerical input state. This indicates within which threshold
band the field input is in and module channel fault status.

Channel

Description

1

Field input channel 1 state

2

Field input channel 2 state

40

Field input channel 40 state

Table 6 Rack 2: STATE descriptions

The numerical input state is returned as an integer value.

Value

Description

8-15

Internal channel fault on module

7

Unknown

6

Over-range

5

High-High

4

High

3

Normal

2

Low

1

line fault

0

Underrange

Table 7 Rack 2: STATE bit descriptions

The input channel has a value 7 (Unknown) when:

1. The input channel cannot be correctly measured by two or more slices of the TMR input

module.

2. The TMR Processor detects a 2-oo-3 channel discrepancy between the three slices of the

TMR input module.

3. The module is simulated (not installed or the TMR Processor cannot communicate with 2-oo-

3 slices of the module).