Simple apparatus is defined as a device which neither generates nor

stores more than 1.2V, 0.1 A, 20 mJ, or 25 mW.



Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.



This module, 1797-IRT8, must be used with terminal base 1797-TB3 or

1797-TB3S.



Terminals 36 and 49 shall not be connected.

WARNING

Substitution of components may impair intrinsic safety.

AVERTISSEMENT

La substitution de composant peut compromettre la
securite intrinseque.