10 Micro800 4-channel Thermocouple/RTD Input Module
Publication 2085-IN007A-EN-P - September 2012
Input type
Thermocouple type: B, C, E, J, K, TXK/XK (L), N, R, S, T
RTD type:
100
Ω
Pt
α
= 0.00385 Euro
200
Ω
Pt
α
= 0.00385 Euro
100
Ω
Pt
α
= 0.003916 U.S
200
Ω
Pt
α
= 0.003916 U.S.
100
Ω
Nickel 618
200
Ω
Nickel 618
120
Ω
Nickel 672
10
Ω
Copper 427
mV range: 0…100 mV
Ohm input: 0…500
Ω
Resolution
16 bits
Channel update time, typical
12…500 ms per enabled channel
Input impedance
> 10 M
Ω
Power dissipation, total
2 W
Enclosure type rating
None (open-style)
Status indicators
1 health status indicators
Isolation voltage
50V (continuous), Reinforced Insulation Type, channel to system.
Type tested at 720V DC for 60 s
North American temp code
T4
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines,
publication
(2)
RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)
Temperature, surrounding air, max
65 °C (149 °F)
Temperature, non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Shock, non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g – DIN rail mount
35 g – Panel mount
General Specifications
Attribute
Value