Mount the module, Module spacing, Status indicators – Rockwell Automation 2080-LC30-16AWB_16QWB_16QVB Micro830 16 Point Programmable Controllers Installation Instructions User Manual
Page 8
8 Micro830 16 Point Programmable Controllers
Publication 2080-IN003B-EN-P - April 2014
Status Indicators
Mount the Module
Most applications require installation in an industrial enclosure to reduce the effects of electrical
interference and environmental exposure. Locate your controller as far as possible from power
lines, load lines, and other sources of electrical noise such as hard-contact switches, relays, and
AC motor drives. For more information on proper grounding guidelines, see the Industrial
Automation Wiring and Grounding Guidelines, publicat
.
Mounting Dimensions and DIN Rail Mounting
Module Spacing
Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown. An exception to this
spacing guideline is allowed for the side at which you are connecting the optional power supply,
2080-PS120-240VAC.
Input status
Run status
Force status
Power status
Fault status
Output status
Serial communications
status
45031
45032
Mounting dimensions do not include mounting feet or DIN rail latches.
100 mm (3.94 in.)
80 mm (3.15 in.)
90 mm (3.54 in.)